Permit NumberFIR13-00184
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 8055 W GODDARD RD
Project NameCapital High School Hallway Re
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of providing partial fire protection and stub ins for future use.

Plan Mod #1 – 8/15/2013
Pipe routing modifications due to field changes
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/22/20138/22/20138/22/2013PPASS
DetailsTroy Cobbley
Permit finaled
Issue and Print Permit  8/22/2013 DONE
DetailsRita DeYoung
this is a plan mod, customer needs inspection in area not affected by mod.
CHANGE STATUS TO (ISS)  8/22/2013 DONE
DetailsTisha Gallop
status should have been changed to issued not ready...plan mod approved and paid for.
Sprinkler Plan Check8/21/2013 8/21/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  8/21/2013 DONE
DetailsTim Frost
Permit Ready to Issue  8/21/2013  
Inspection Record Card- Fire8/21/2013 8/21/2013 DONE
DetailsDarla L Downs
(F) Reprint permit  8/21/2013 DONE
Sprinkler Plan Check8/15/2013 8/15/2013 FAIL
DetailsTim Frost
Miscellaneous action  8/15/2013 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
INSP-Sprinkler Rough-in/Hydro8/7/20138/13/20138/13/2013APASS
DetailsTroy Cobbley
It took two inspections but the overhead hydro passed.
INSP-Sprinkler Rough-in8/5/20138/6/20138/6/2013PPASS
DetailsTroy Cobbley
Todays inspection verified that the seismic bracing had been installed on the gridded system in the Cafeteria. This included the branchlines and the far main.
INSP-Sprinkler Rough-in8/1/20138/5/20138/5/2013PPART
DetailsTroy Cobbley
Todays inspection was for the remaining first floor east corridor which has not been connected but is ok to cover. Also todays inspection was for the cafeteria which was already covered. Seismic bracing is missing on the branch lines and the 1 1/2" far main. Also the pipe routing has been modified for the branchlines and the new arm overs to the pendant heads. Plan modifications are required showing all of these changes and all of the other piping changes through-out the new system. Include the sprinkler heads model changes and revised hydraulic calculations.
INSP-Sprinkler Rough-in8/1/20138/5/20138/1/2013PCANC
DetailsTroy Cobbley
We need a 1st floor inspection. Please call Bruce 30 mins prior. Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
Miscellaneous action  8/1/2013 DONE
Switched Tyco extended coverage 11.2K sprinklers to Viking extended coverage 11.2K sprinklers
Coverage matched so the switch was OK
INSP-Sprinkler Rough-in/Hydro7/26/20137/29/20137/29/2013PPASS
DetailsTroy Cobbley
See the city approved plans for the first floor areas where the sprinkler piping is ok to cover. Plan modifications may be needed showing the different sprinkler pendants installed and pipe routing changes. Contractor needs to have a conversation with the sprinkler plan reviewer to get a resolution.
INSP-Sprinkler Rough-in7/15/20137/16/20137/16/2013PPART
DetailsTroy Cobbley
RTC 2nd floor is mostly ok. Contractor needs to get with plan review but it appears a plan modification is needed since viking pendants were installed instead of tyco. Also the earthquake bracing has not been installed as shown on the plans. I'm ok with the second floor lay-in tile being installed in all locations except where I will need to view earth quake bracing.
INSP-Sprinkler Rough-in6/10/20136/11/20136/11/2013ACANC
DetailsTroy Cobbley
troy or joe @ ###-#### Phone #: ###-####
Sprinkler Plan Check5/15/2013 5/15/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  5/15/2013 DONE
DetailsTim Frost
Permit Ready to Issue  5/15/2013 DONE
DetailsChristina Prado
Issue and Print Permit  5/15/2013 DONE
DetailsChristina Prado
Inspection Record Card- Fire5/15/2013 5/15/2013 DONE
DetailsChristina Prado
Miscellaneous action  5/9/2013 DONE
Call and asked for the correct drawing. The one that was supplied was named incorrectly.
1st review completed  5/1/2013 FAIL
Sprinkler Plan Check5/1/2013 5/1/2013 FAIL
DetailsTim Frost
Plan assigned to (Tim)5/1/2013 5/1/2013 DONE
DetailsTim Frost
Application received  4/24/2013 DONE
Application submitted via PDS Online on Apr 24 2013 9:35AM