Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR13-00204
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3233 N COLE RD
Project NameWalMart Neighborhood Market
Customer Number 
ePlanReviewYes
Description
Demo all existing sprinkler system back to the flange above floor. Reinstall new fire sprinkler systems per the engineered drawings provided by Henderson Engineers Inc.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/9/20139/10/20139/11/2013APASS
DetailsForrest France
Forward flow testing completed satisfactory.
INSP-Final Inspection9/6/20139/9/20139/9/2013PDEFR
DetailsForrest France
Please call 1/2 hr prior to inspection. Mike B is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Final Inspection9/5/20139/6/20139/6/2013PFAIL
DetailsTroy Cobbley
Need forward flush to final.
INSP-Sprinkler Rough-in/Hydro8/14/20138/16/20138/16/2013PPASS
DetailsTroy Cobbley
The overhead hydro test passed
INSP-Sprinkler Rough-in/Hydro8/9/20138/12/20138/12/2013AFAIL
DetailsTroy Cobbley
Hydro test failed due to a visible drop in pressure at the guage. Also sprinkler coverage has not been installed under an overhead door. This work will need to be done prior to a hydro test.
INSP-Sprinkler Rough-in/Hydro8/8/20138/9/20138/9/2013PNR
DetailsForrest France
Hydrostatic test incompleted due to system leakage in need of repair.
INSP-Sprinkler Rough-in8/2/20138/5/20138/5/2013APART
DetailsTroy Cobbley
The retail area ceilings are ok to cover piping. I noted one location where pendant mount lighting is blocking the pendant sprinkler heads. The three time rule of NFPA 13 chapter 8 should apply.
INSP-Sprinkler Rough-in7/22/20137/23/20137/23/2013APASS
DetailsTroy Cobbley
Todays inspection was to verify that the insulation had been repaired at the deck and was no longer obstructing the upright sprinkler heads. All areas had been repaired except for three locations. I will verify these three at the next rough-in inspection.
INSP-Sprinkler Rough-in7/3/20137/5/20137/5/2013APART
DetailsTroy Cobbley
Todays inspection was for the hangers and piping which passed except Nate is going to add two branchline restraints for me. A separate inspection will be needed for approval to cover. As of today insulation is blocking the upright sprinkler coverage in many locations and the ceiling "t bar" has not been installed yet to verify actual pendant head layout.
INSP-Sprinkler Rough-in7/2/20137/3/20137/3/2013ACANC
DetailsTroy Cobbley
Cancel per Nate
INSP-Sprinkler Rough-in6/18/20136/19/20136/19/2013PPART
DetailsForrest France
Okay to cover ceilings at the mens, womens, family and pharmacy restrooms as marked and dated on stamped plans. Discussed coverage at the coolers, UG fire supply flush post demo.
Override - Parcel Holds6/18/20131/1/19006/18/2013  
fir r/i
INSP-Sprinkler Rough-in6/14/20136/17/20136/17/2013APART
DetailsForrest France
Overhead work okay to cover at the cash room and entry vestibule.
INSP-Sprinkler Rough-in6/13/20136/14/20136/14/2013PFAIL
DetailsForrest France
Inspection for sheetrock ceiling cover at the cart storage and cash rooms only- Draft stop above the cart storage area ceiling creates an obstruction to upright sprinkler coverage, noted mixed temp. heads are installed at the cart storage room absent of a specific heat source, missing approved plans on site.
Override - Parcel Holds6/14/20131/1/19006/14/2013  
fire r/i
Override - Parcel Holds6/13/20131/1/19006/13/2013  
fire sprinkler r/i
Sprinkler Plan Check6/4/2013 6/4/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  6/4/2013 DONE
DetailsTim Frost
Override - Parcel Holds  6/4/2013  
Inspection Record Card- Fire6/4/2013 6/4/2013 DONE
DetailsBarbara Stitt
Override - Parcel Holds  6/4/2013  
Issue and Print Permit  6/4/2013 DONE
DetailsBarbara Stitt
Miscellaneous action  5/28/2013 DONE
Sent email to Tom Easton as follows

Tom,

The letter you provided is insufficient for several reasons.

The chart in the top right of drawing FP-3 indicates the Tenant space/Deli/Pharmacy/Miscellaneous Storage is design as a class IV. Where are these item received? Is there a separate receiving area for these commodities? If not then why is the receiving area not designed for these commodities (Class IV)?

The storage shall be designed for the highest commodity. See section highlighted below.

IFC: 2304.1 General.
High-piled storage areas , and portions of high-piled storage areas intended for storage of a different commodity class than adjacent areas, shall be designed and specifically designated to contain Class I, Class II, Class III, Class IV or high-hazard commodities. The designation of a high-piled combustible storage area, or portion thereof intended for storage of a different commodity class, shall be based on the highest hazard commodity class stored except as provided in Section 2304.2.

There is an exception that permits an engineering analysis. The letter does not comply with the required analysis. Please, see below.

IFC: 2304.2 Designation based on engineering analysis.
The designation of a high-piled combustible storage area, or portion thereof, is allowed to be based on a lower hazard class than that of the highest class of commodity stored when a limited quantity of the higher hazard commodity has been demonstrated by engineering analysis to be adequately protected by the automatic sprinkler system provided. The engineering analysis shall consider the ability of the sprinkler system to deliver the higher density required by the higher hazard commodity. The higher density shall be based on the actual storage height of the pile or rack and the minimum allowable design area for sprinkler operation as set forth in the density/area figures provided in NFPA 13. The contiguous area occupied by the higher hazard commodity shall not exceed 120 square feet (11
m2) and additional areas of higher hazard commodity shall be separated from other such areas by 25 feet (7620 mm) or more. The sprinkler system shall be capable of delivering the higher density over a minimum area of 900 square




? Provide a minimum of Class IV protection for the Receiving Area, Tenant space, Deli, Pharmacy, Miscellaneous Storage.

? Provide additional hydraulic calculation for the above areas complying with (Ref: NFPA 13: 12.3)

? The Owner’s Certificate indicated that there will be idle pallet storage. Please, correlate the fire protection design with (Ref: NFPA 13: 12.12)





Cordially,

Tim Frost, S.E.T.
Fire Sprinkler Plans Examiner
Fire Code Plans Examiner
Fire Inspector

City of Boise
tfrost@cityofboise.org
###-####
Miscellaneous action  5/22/2013 DONE
DetailsTim Frost
Emailed review to contractor
Early Start  5/22/2013 FAIL
Email to applicant:

Tom,

I have to deny the early start request. Item 3 in my review (below) is too significant of an item. In addition, I have not seen an Owner’s Certificate to reevaluate my opinion.

Normally, Early Start Request is only approved for extenuating circumstance. I do not feel this is the case in this project.



A Class IV commodity shall be defined as a product, with or without pallets, that meets one of the following criteria:
(1) Constructed partially or totally of Group B plastics
(2) Consists of free-flowing Group A plastic materials
(3) Contains within itself or its packaging an appreciable amount 5 percent to 15 percent by weight or 5 percent to 25 percent by volume) of Group A plastics (Ref: NFPA 13: .6.3.4.1)

To determine the acceptability of technologies, processes, products, facilities, materials and uses attending the design, operation or use of a building or premises subject to inspection by the fire code official , the fire code official is authorized to require the owner or agent to provide, without charge to the jurisdiction, a technical opinion and report. The opinion and report shall be prepared by a qualified engineer, specialist, laboratory or fire safety specialty organization acceptable to the fire code official and shall analyze the fire safety properties of the design, operation or use of the building or premises and the facilities and appurtenances situated thereon, to recommend necessary changes. The fire code official is authorized to require design submittals to be prepared
by, and bear the stamp of, a registered design professional. (Ref: IFC: 104.7.2)

Resubmit – 5/21/2013: Provide a signed and seal letter from a FPE indicating the rack storage receiving area will only contain Class I-III commodities. Based on my observation, of other Wal-Mart stores it would seem they contain Class IV commodities and Group A plastic. (Please, see the example list in the appendix of NFPA 13 for further reference.)


Cordially,

Tim Frost, S.E.T.
Fire Sprinkler Plans Examiner
Fire Code Plans Examiner
Fire Inspector

City of Boise
tfrost@cityofboise.org
###-####
Sprinkler Plan Check5/21/2013 5/21/2013 FAIL
DetailsTim Frost
1st review completed  5/21/2013 FAIL
Plan assigned to (Tim)5/6/2013 5/6/2013 DONE
DetailsTim Frost
Miscellaneous action  5/6/2013 FAIL
Failed prescreen review.
Owner's Certificate
Water Supply Information from water purveyor
High Pile Storage Form
Sheet orientation
Application received  5/3/2013 DONE
Application submitted via PDS Online on May 3 2013 3:10PM
Early Start  4/14/2013 PASS
Demo ONLY
See attachecd