INSP-Final Inspection | 6/18/2013 | 6/19/2013 | 6/19/2013 | A | PASS |
Forrest France
|
|
|
Noted correction items finished. Fire alarm testing passed, permit finaled.
|
INSP-Final Inspection | 6/17/2013 | 6/18/2013 | 6/18/2013 | A | FAIL |
Forrest France
|
|
|
Inaccurate floorplan/room usage is shown. Provide notification at the conference and breakroom areas.
|
Issue and Print Permit | | | 5/31/2013 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/24/2013 | | 5/24/2013 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 5/24/2013 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 5/24/2013 | | DONE |
Barbara Stitt
|
|
|
Called and told permit is ready & fees due on 5-24-13 @ 8:55am//BAS
|
Plan assigned to (Stephanie) | 5/9/2013 | | 5/23/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Miscellaneous action | | | 5/23/2013 | | DONE |
|
|
|
Received requested information
|
Alarm Plan Check | 5/23/2013 | | 5/23/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
plans approved with review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 5/23/2013 | | DONE |
|
|
|
approved plans taken to permit technician for processing
|
1st review completed | | | 5/23/2013 | | PASS |
|
|
|
|
1st review completed | | | 5/21/2013 | | PEND |
|
|
|
Need revised calcs but have not yet heard from the designer.
|
Miscellaneous action | | | 5/20/2013 | | DONE |
|
|
|
sent an email to Mary Froemke asking for the capacity and data sheet for the amp the speakers are being tied in to. She responded that it is a 50W amp. I sent an email back letting her know I needed new calcs because the ones submitted with the packet indicate there are a total of 146watts being used.
|
Application received | | | 5/9/2013 | | |
|
|
|
|