Case Summary | | | 1/30/2014 | | DONE |
|
|
|
|
INSP-Final Inspection | 10/29/2013 | 11/1/2013 | 11/6/2013 | A | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Final Inspection | 10/29/2013 | 10/30/2013 | 10/29/2013 | A | CANC |
Forrest France
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton *Wrong permit number request*
|
Plan resubmittals received | | | 7/31/2013 | | DONE |
Tisha Gallop
|
|
|
received one copy of as-builts; taken to Lee
|
INSP-Final Inspection | 7/26/2013 | 7/29/2013 | 7/29/2013 | P | PART |
Forrest France
|
|
|
Final pending as-built plans including accurate address points, additional duct SD, revised matrix, post map at the panel, provide record of completion forms. Functional testing passed.
|
INSP-Final Inspection | 7/26/2013 | 7/26/2013 | 7/26/2013 | P | NR |
Forrest France
|
|
|
Dave Phone #: ###-####
|
Miscellaneous action | | | 7/26/2013 | | DONE |
Lee G Meredith
|
|
|
Informed by Troy James that the heat pumps cover more of the building than the recently added smoke detection covers. I called the designer and informed them that modifications will need to be made again to provide accurate smoke detection coverage for the areas that heat pumps 1 - 3 serve. I called the inspector to inform them of the new information. The general contractor came by city hall to inform us that their interpretation of the IMC allowed open area detection in the room where the heat pump air intake was located. Troy and I met with them to inform them that the exception of using the room as an open plenum to minimize detection requirements was not being met, since the room was occupiable This exception is only allowed in an unoccupiable room. I informed them that each heat pump would require an approved method of return air detection. This would include individual duct smoke detectors with sample tubes or individual detectors at the intake of each heat pump. If individual detectors are used, they must be rated for the feet per minute of airflow to be experienced at each location and that in the plan modification that is required, this information will be required. I called the designeer to inform them of the same information.
|
Telephone call | | | 7/26/2013 | | DONE |
Lee G Meredith
|
|
|
Mary Froemke called requesting requirements on duct detector information for resubmittal. I informed her that we could accept as built record drawings for documentation of the detectors located at heat pumps above meeting room 112 and that we will require documentation that indicates the intake air flow for each heat pump (1-3). According to the product data for the detectors being used, they are rated for an air flow velocity of 0 - 400 feet per minute. The intake for the heat pumps cannot exceed this amount. If they do, traditional duct smoke detectors will be required.
|
Plan resubmittals received | | | 7/24/2013 | | |
|
|
|
Plan Modification
|
Plan assigned to (Lee) | 7/24/2013 | | 7/24/2013 | | DONE |
Lee G Meredith
|
|
|
Plan modification
|
Plan resubmittals received | | | 7/24/2013 | | DONE |
Lee G Meredith
|
|
|
Plan Mod - relocate FACP and associated detector to electrical room. Add full area smoke detection to meeting room and control module for HP1-3 shutdown.
|
Plan assigned to (Lee) | 7/24/2013 | | 7/24/2013 | | DONE |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 7/24/2013 | | 7/24/2013 | | PASS |
Lee G Meredith
|
|
|
Existing review notes still apply and are unchanged.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/24/2013 | | DONE |
Lee G Meredith
|
|
|
Approved plans taken to front desk. Project updated.
|
Permit Ready to Issue | | | 7/24/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 7/24/2013 | | 7/24/2013 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 7/24/2013 | | DONE |
Christina Prado
|
|
|
called Patrick to advise permit is ready for pick up and gave fees due
|
(F) Reprint permit | | | 7/24/2013 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 7/24/2013 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 7/22/2013 | | DONE |
Lee G Meredith
|
|
|
Informed by Troy James of mechanical inspections that there may be some air handlers that exceed the minimal requirement for duct smoke detectors. I called the vendor Patrick Gill of EEG (###-####) and left a message for him to call me for further discussion.
|
Inspection Record Card- Fire | 5/24/2013 | | 5/24/2013 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 5/24/2013 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 5/24/2013 | | DONE |
Barbara Stitt
|
|
|
Called permits told permit is ready & fees due on 5-24-13 @ 8:50am//BAS
|
Issue and Print Permit | | | 5/24/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 5/15/2013 | | 5/23/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 5/23/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 5/23/2013 | | 5/23/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
plans approved with review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 5/23/2013 | | DONE |
|
|
|
approved plans taken to permit technician for processing
|
Application received | | | 5/15/2013 | | |
|
|
|
|