Permit Information
Permit NumberFIR13-00218
StatusIssued
Name TREASURE VALLEY FIRE PROTECTION
Site Address 300 N MILWAUKEE ST
Project NameJC Penneys TI @ BTS
Customer Number 
ePlanReviewYes
Description
Add, Relocate or Delete sprinklers to accommodate new ceiling
elevations and or wall modifications
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIR-Aging Inspection7/20/20177/20/20177/25/2017 NR
DetailsTroy Cobbley
Still waiting for follow up from Jeff
FIR-Aging Inspection2/23/20162/23/20162/26/2016 NR
DetailsTroy Cobbley
Jeff is following up
INSP-Sprinkler Rough-in6/26/20136/27/20136/27/2013APART
DetailsTroy Cobbley
I found some of the pendant sprinkler protection had been modified as per the last on site conference but several location the heads had not been modified to match plan so they remain out of code compliance. I found several areas with overspaced heads, which per the sprinkler fitter stated were outside of his scope of work. After speaking to Tim Frost on the soffits and cabinetry we are of the opion to meet NFPA 13 4.1 , that the sprinkler coverage is to be provided behind/extend to the wall behind the soffit. The cabinetry appears to be mobile. Tim spoke to Brad at TVFP about the issue. It also appears that a plan modification will be required since the wall and soffit and sprinkler head installation\layout does not match the city approved plans.
INSP-Sprinkler Rough-in6/17/20136/18/20136/18/2013AFAIL
DetailsForrest France
Missing approved plans and review comments on site, rough-in inspection has not been requested prior to completion of ceiling cover, pendent heads in need of adjustment- missing escutcheons at several locations, noted blocked and obstructed heads due to lighting tray and shelved merchandise displays adjacent to walls.
INSP-Sprinkler Rough-in6/10/20136/10/20136/10/2013PFAIL
DetailsTroy Cobbley
javier and I started the inspection but I found not all of the heads as shown on the plans have been installed and some of the pendants installed are blocked by signage/racking at the new soffits. Also I looked at some work that is not shown on the plans.
Permit Ready to Issue  5/22/2013  
Inspection Record Card- Fire5/22/2013 5/22/2013 DONE
DetailsDarla L Downs
Issue and Print Permit  5/22/2013 DONE
Sprinkler Plan Check5/21/2013 5/21/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  5/21/2013 DONE
DetailsTim Frost
Plan assigned to (Tim)5/20/2013 5/20/2013 DONE
DetailsTim Frost
Sprinkler Plan Check5/20/2013 5/20/2013 FAIL
DetailsTim Frost
1st review completed  5/20/2013 FAIL
DetailsTim Frost
Application received  5/17/2013 DONE
Application submitted via PDS Online on May 17 2013 1:40PM