INSP-Final Inspection | 12/6/2013 | 12/9/2013 | 12/9/2013 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 12/4/2013 | 12/5/2013 | 12/5/2013 | A | PASS |
Troy Cobbley
|
|
|
Underground flush passed
|
INSP-Sprinkler Rough-in | 6/17/2013 | 6/17/2013 | 6/17/2013 | P | PART |
Forrest France
|
|
|
UG fire supply pipe from the property line at the point of connection to the stub-in/riser approved for bury.
|
Permit Ready to Issue | | | 6/17/2013 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 6/17/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 6/17/2013 | | 6/17/2013 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (Tim) | 6/14/2013 | | 6/14/2013 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/14/2013 | | 6/14/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 6/14/2013 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/14/2013 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 6/14/2013 | | DONE |
|
|
|
Sent Email to Brodie as follows:
Brodie,
Please, keep in mind, that you will need to comply with the below
903.1.2 SPRINKLER SYSTEM CONTROL VALVE LOCATION AND SIGNS.
Unless specifically approved by the code official, the fire sprinkler system main control valve(s) (Ref: NFPA BMC:903.1.2)
shall be installed in any one of the following configurations:
1. A Post Indicator Valve (PIV). Where practical a PIV shall be installed at least 40 feet from the building.
2. A Wall Post Indicator Valve (WPIV).
3. A valve(s) installed on the riser itself provided the sprinkler riser room is separated from the building on all sides by a one-hour Occupancy Separation assembly, including opening and penetration protection, as defined by the Building Code. In addition to any other access doors, direct access into the riser room from the outside shall be provided. Signs identifying doors leading to the sprinkler system control assembly shall be permanently affixed to all doors so as to clearly identify the path to the riser assembly.
The valve configurations required in this section are listed in order of preference, not in order of requirement.
Note: An exception is given for single family dwellings to locate the riser in the garage.
Cordially,
Tim Frost, S.E.T.
Fire Sprinkler Plans Examiner
Fire Code Plans Examiner
Fire Inspector
City of Boise
tfrost@cityofboise.org
###-####
|
Application received | | | 6/13/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 13 2013 3:17PM
|