INSP-Final Inspection | 9/19/2013 | 9/20/2013 | 9/20/2013 | A | PASS |
Forrest France
|
|
|
C/N items finished. Reinspection passed. Fire sprinkler permit finaled.
|
INSP-Final Inspection | 9/18/2013 | 9/19/2013 | 9/19/2013 | A | CANC |
Forrest France
|
|
|
Need trip test and Final sprinkler system inspection. Please contact Richard Clark ###-#### for questions. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 9/12/2013 | 9/13/2013 | 9/13/2013 | A | PART |
Forrest France
|
|
|
Remainder of C/N items verified for completion. System two trip tested at 1 min. 6 seconds. System one trip tested at 2 min 15 sec. and will require the addition of a QOD. Quick trip of the new dry valve passed.
|
INSP-Sprinkler Rough-in | 9/11/2013 | 9/12/2013 | 9/12/2013 | A | PART |
Forrest France
|
|
|
Items on the previous correction notice are not yet finished at some locations including ssu's at the ramp, missing seismic brace, missing section of galv pipe, trapped outlet. Verified missing coverage has been added, hangers adjusted, head cages on, adjustments, etc. are finished. New valve and trim monitoring not yet finished. Discussed trip test schedule.
|
INSP-Sprinkler Rough-in/Hydro | 8/29/2013 | 8/30/2013 | 8/30/2013 | A | PART |
Forrest France
|
|
|
Completed hydrostatic testing of the new dry system piping serving the north half of the parking garage. Also finished systems walkthrough and noted items in need of revision, adjustment or repair including missing or overspaced upright protection at four locations, duct and hanger obstructions, three sprigs too far below the deck, one missing EQ brace, one trapped outlet, provide head cage at SW head, one section of 3" main is not yet replaced with galv. Ref. annotations on plans.
|
INSP-Sprinkler Rough-in/Hydro | 8/27/2013 | 8/29/2013 | 8/29/2013 | P | PART |
Forrest France
|
|
|
Completed hydrostatic testing of the new dry system serving the south half of the parking garage.
|
Issue and Print Permit | | | 7/1/2013 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Fire | 7/1/2013 | | 7/1/2013 | | DONE |
Tisha Gallop
|
|
|
|
Sprinkler Plan Check | 6/28/2013 | | 6/28/2013 | | FAIL |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/28/2013 | | 6/28/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/28/2013 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/27/2013 | | 6/27/2013 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 6/27/2013 | | FAIL |
Tim Frost
|
|
|
|
Plan assigned to (Tim) | 6/24/2013 | | 6/24/2013 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 6/14/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 14 2013 10:58AM
|