Permit Information
Permit NumberFIR13-00314
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 801 W MAIN ST
Project NameLucky Fins Seafood Grill
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/6/2014 DONE
DetailsTim Frost
Sent to Records for scanning.
INSP-Final Inspection9/12/20139/13/20139/13/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection9/6/20139/9/20139/12/2013PPART
DetailsForrest France
INSP-Sprinkler Rough-in8/26/20138/26/20138/26/2013PFAIL
DetailsTim Frost
Failed - One sprinkler missing in the foyer to the kitchen area. Unable to verify if pipe sizes were changed. Ceiling tile was installed. No fitter on job site. Could not verify if the sidewall sprinkler below the garage door was extended throw type. Sprinklers were space slightly different from what was shown but appear to be adequate.
INSP-Sprinkler Rough-in8/22/20138/23/20138/23/2013APART
DetailsForrest France
Fire sprinkler work above drop ceilings in the seating area, second floor office, storage and stairway are approved for cover per dated annotations on approved plans.
INSP-Sprinkler Rough-in8/1/20138/2/20138/2/2013APASS
DetailsTroy Cobbley
The supply piping that was installed as 1" has been correct to match the required 1 1/4". The piping in the restroom walls can now be covered.
INSP-Sprinkler Rough-in8/1/20138/1/20138/1/2013PPART
DetailsTroy Cobbley
Soffits as marked "ok" in red are ok to cover. But acouple issues need to be addressed which include the branchline supply piping to the heads in the east side soffit is shown on the plans as 1 1/4 but 1" has been installed (4 heads are being supplied). Also the supply piping for the sidewalls is shown to be 1 1/4" but only 1" has been installed (3 heads are being supplied). Soffits are ok to cover but piping needs to be installed as approved or plan modifications are needed for the pipe size changes.
Plan assigned to (Tim)7/16/2013 7/31/2013 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  7/31/2013 DONE
DetailsTim Frost
Inspection Record Card- Fire7/31/2013 7/31/2013 DONE
DetailsDarla L Downs
Permit Ready to Issue  7/31/2013  
Telephone call  7/31/2013  
7-31-13 called American Fire Protection permit ready and fee given ///dld
Issue and Print Permit  7/31/2013 DONE
Plan resubmittals received  7/26/2013 DONE
DetailsChristina Prado
received three sets of revices plans, calcs and apps taken to Tim for further review
Sprinkler Plan Check7/19/2013 7/19/2013 FAIL
DetailsTim Frost
1st review completed  7/19/2013 FAIL
DetailsTim Frost
Telephone call  7/19/2013 DONE
DetailsTisha Gallop
called american fire protection and told them denied plans at front desk
Application received  7/16/2013  
Case Summary  7/16/2013 DONE