INSP-Final Inspection | 11/15/2013 | 11/18/2013 | 11/18/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 11/12/2013 | 11/15/2013 | 11/15/2013 | P | FAIL |
Troy Cobbley
|
|
|
Everything is ok except the alarm bell needs to be relocated to the side of the building where the FDC is located
|
INSP-Sprinkler Rough-in/Hydro | 10/22/2013 | 10/23/2013 | 10/23/2013 | A | PASS |
Troy Cobbley
|
|
|
Second floor hydro test passed
|
INSP-Sprinkler Rough-in/Hydro | 10/21/2013 | 10/22/2013 | 10/22/2013 | A | PART |
Troy Cobbley
|
|
|
First floor hydro passed. Second floor failed due to visible leak on the riser.
|
INSP-Sprinkler Rough-in | 10/4/2013 | 10/4/2013 | 10/4/2013 | P | PASS |
Troy Cobbley
|
|
|
Overhead rough-in passed. Piping can be covered. Riser not complete yet. Underground flush passed. FDC is mounted too high and will need to be lowered.
|
INSP-Sprinkler Rough-in | 10/3/2013 | 10/3/2013 | 10/3/2013 | P | CANC |
Troy Cobbley
|
|
|
I noted that the FDC was not located on the street side of the building. So Mike wanted to just reschedule for tomorrow.
|
INSP-Sprinkler Rough-in | 8/12/2013 | 8/14/2013 | 8/14/2013 | P | PASS |
Troy Cobbley
|
|
|
Underground supply piping is ok to cover. Its 2" poly like all of the others.
|
Sprinkler Plan Check | 8/2/2013 | | 8/2/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/2/2013 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 8/2/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 8/2/2013 | | 8/2/2013 | | DONE |
Darla L Downs
|
|
|
|
Issue and Print Permit | | | 8/2/2013 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 7/29/2013 | | 7/29/2013 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/29/2013 | | 7/29/2013 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 7/29/2013 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 7/29/2013 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Application received | | | 7/24/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 24 2013 9:04AM
|