Permit Information
Permit NumberFIR13-00359
StatusFinaled
Name JBL FIRE PROTECTION LLC
Site Address 10051 W SMOKE RANCH DR
Project NameUnion Square Phase 2 Bldg. 14
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting a new 3 level residential building per NFPA 13R
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/2/20141/6/20141/6/2014APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in9/24/20139/24/20139/25/2013PPASS
DetailsTroy Cobbley
Tenting has been corrected and piping can be covered.
INSP-Sprinkler Rough-in9/23/20139/24/20139/24/2013AFAIL
DetailsTroy Cobbley
Tenting still is not repaired. Piping can not be covered.
INSP-Sprinkler Rough-in9/16/20139/16/20139/16/2013PFAIL
DetailsTroy Cobbley
Several locations need the tenting modified to provide coverage of the sprinkler piping.
INSP-Sprinkler Rough-in9/12/20139/12/20139/12/2013PPASS
DetailsTroy Cobbley
The pipe routing now matches the plan modifications. Still need a tenting inspection on the third floor. Overspaced pendants on the first and second floors have been corrected.
INSP-Sprinkler Rough-in/Hydro9/12/20139/12/20139/12/2013PPASS
DetailsTroy Cobbley
Overhead hydro passed for all floors.
INSP-Sprinkler Rough-in9/10/20139/11/20139/11/2013PPART
DetailsTroy Cobbley
Plans need to be resubmitted due to extensive pipe routing changes on the first and second floors. Third floor piping matches but can not be covered until a tenting inspection has been passed. I noted eight overspaced heads on the first and second floors at the east and west end bedrooms (see marked plans). All in all no piping can be covered yet.
Miscellaneous action  9/11/2013 DONE
Reviewed As Built drawing in ProjectDox. Everything checked out.
Permit Ready to Issue  8/23/2013  
Inspection Record Card- Fire8/23/2013 8/23/2013 DONE
DetailsDarla L Downs
Issue and Print Permit  8/23/2013 DONE
Inspection Record Card- Fire8/23/2013 8/23/2013 DONE
DetailsDarla L Downs
Issue and Print Permit  8/23/2013 DONE
(F) Reprint permit  8/23/2013 DONE
(F) Reprint permit  8/23/2013 DONE
Sprinkler Plan Check8/6/2013 8/6/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  8/6/2013 DONE
DetailsTim Frost
Plan assigned to (Tim)8/1/2013 8/1/2013 DONE
DetailsTim Frost
Sprinkler Plan Check8/1/2013 8/1/2013 FAIL
DetailsTim Frost
1st review completed  8/1/2013 FAIL
DetailsTim Frost
Miscellaneous action  8/1/2013 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Application received  7/27/2013 DONE
Application submitted via PDS Online on Jul 27 2013 1:20PM