INSP-Final Inspection | 11/4/2013 | 11/4/2013 | 11/4/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/31/2013 | 11/1/2013 | 11/1/2013 | P | FAIL |
Craig D. Hanson
|
|
|
FA not ready.
|
INSP-Sprinkler Rough-in/Hydro | 10/25/2013 | 10/25/2013 | 10/25/2013 | P | PASS |
Craig D. Hanson
|
|
|
|
INSP-Sprinkler Rough-in | 10/24/2013 | 10/24/2013 | 10/24/2013 | P | PART |
Troy Cobbley
|
|
|
Pendant sprinkler heads are overspaced in three of the below mezzanine offices. Piping can be covered and the spacing will be verified at the final inspection. Sprinkler rough-in passed in the lobby area and the second floor area.
|
INSP-Sprinkler Rough-in | 10/21/2013 | 10/22/2013 | 10/22/2013 | A | PASS |
Troy Cobbley
|
|
|
Piping above hard lids is ok to cover. Sprinkler piping rough-in for below the mezzanine piping and the overhead hanger piping passed.
|
Sprinkler Plan Check | 10/16/2013 | | 10/16/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/16/2013 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 10/16/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 10/16/2013 | | 10/16/2013 | | DONE |
Darla L Downs
|
|
|
|
Issue and Print Permit | | | 10/16/2013 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/5/2013 | | 9/5/2013 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 9/5/2013 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Sprinkler Plan Check | 8/6/2013 | | 8/6/2013 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 8/6/2013 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 8/6/2013 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Miscellaneous action | | | 8/5/2013 | | DONE |
|
|
|
Sent email requesting addtional information to clarify if the hangar qualifies for the exception to foam.
|
Plan assigned to (Tim) | 8/5/2013 | | 8/5/2013 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 7/29/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 29 2013 10:40AM
|