INSP-Final Inspection | 9/16/2013 | 9/18/2013 | 9/18/2013 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 8/14/2013 | 8/14/2013 | 8/14/2013 | P | PASS |
Forrest France
|
|
|
Verified additional upright coverage above the retail area at a perimeter beyond the stockroom wall. Overhead work approved for ceiling cover.
|
INSP-Sprinkler Rough-in | 8/13/2013 | 8/13/2013 | 8/13/2013 | P | PART |
Troy Cobbley
|
|
|
Per the plans the wall separating the stock room from the retail area is full height but in reality it does not. So the three upright sprinkler heads located at the wall will require additional coverage over the ceiling of the retail area. All other work looked ok. Piping is ok to cover as long as access is provided to verify correction.
|
Permit Ready to Issue | | | 8/5/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 8/5/2013 | | 8/5/2013 | | DONE |
Darla L Downs
|
|
|
|
Issue and Print Permit | | | 8/5/2013 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 8/2/2013 | | 8/2/2013 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 8/2/2013 | | 8/2/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 8/2/2013 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/2/2013 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 8/1/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 1 2013 12:41PM
|