Information based on query as of Thursday, July 25, 2024.
Permit Information
Permit NumberFIR13-00436
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 1515 W STATE ST
Project NameRite Aid
Customer Number 
ePlanReviewYes
Description
Retrofit a new calculated pendant sprinkler system to protect the floor area below the proposed new t-bar ceiling at the sales area. Existing ordinary hazard pipe schedule to remain. Recut/replace and relocate the sprinklers at the new propsed pharmacy area. All srinklers at sales floor area to be changed to quick response
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/31/201311/1/201311/1/2013APASS
DetailsForrest France
Scope of work completed. Final walkthrough passed. Flow switch at the existing riser to be repaired prior to project related building permit final.
INSP-Sprinkler Rough-in10/9/201310/9/201310/9/2013PPART
DetailsForrest France
Remainder of the overhead work at the pharmacy and west lower ceiling retail areas passed rough-in and are approved for cover. Verified balance of branchline restraints are installed in the high bays, drops at cloud ceilings okayed. Need to provide coverage at the SW exit vestibule, remove travel caps at drops, install escutcheons and field ceiling tile prior to permit final.
INSP-Sprinkler Rough-in/Hydro9/24/20139/30/20139/30/2013APART
DetailsForrest France
Overhead hydrostatic test completed satisfactory. Also finished rough-in at the high bay sales floor area only- EQ bracing and seismic branchline restraints are not yet finished.
Permit Ready to Issue  9/12/2013  
Inspection Record Card- Fire9/12/2013 9/12/2013 DONE
DetailsDarla L Downs
Issue and Print Permit  9/12/2013 DONE
Sprinkler Plan Check9/6/2013 9/6/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  9/6/2013 DONE
DetailsTim Frost
Sprinkler Plan Check8/28/2013 8/28/2013 FAIL
DetailsTim Frost
1st review completed  8/28/2013 FAIL
DetailsTim Frost
Miscellaneous action  8/28/2013 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Plan assigned to (Tim)8/27/2013 8/27/2013 DONE
DetailsTim Frost
Application received  8/26/2013 DONE
Application submitted via PDS Online on Aug 26 2013 3:12PM