Permit Information
Permit NumberFIR13-00441
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 8458 W ELISA ST
Project NameQuality Door
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting a new warehouse including a small mezzanine. There will be no fabrication. The 6” underground supplies a 4” backflow preventer , 4” riser, 4” main and 1 ½” branch lines. The system layout is a tree type configuration and utilizes extended coverage 20’x20’ sprinklers.

Quality Door and Millwork - To construct a new 15,585 square foot one story with 860 square foot storage mezzanine pre-engineered metal retail and warehouse building and related site improvements. The mezzanine is wood framed construction. This building is fully fire sprinkled. The sprinklers are used for area increase and requirements of IBC, Section 903.2.9. The owner's agent has declared that this building will be used as a warehouse only and the mezzanine will be used as a storage area only. There will be no wood fabrication done at this facility; see the attached response letter from ALC Architects. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro11/15/201311/15/201311/15/2013APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection11/14/201311/15/201311/15/2013AFAIL
DetailsTroy Cobbley
No access to the building interior
INSP-Final Inspection11/15/201311/15/201311/15/2013PPASS
DetailsTroy Cobbley
Pass per Troy
DOC - Permit Finaled  11/15/2013 DONE
DetailsChristina Prado
Miscellaneous action  11/12/2013 DONE
A new sprinkler was approved for this project TYCO TY6137

A letter was submitted indicating the engineer would not approved the hanger from the bottom of the Z purlin.
INSP-Final Inspection11/7/201311/8/201311/8/2013PFAIL
DetailsTroy Cobbley
Tyco heads have been installed instead of the submitted Viking, provide one additional brace at the end of the 4" main and provide letter from manufacturer to support the installation of the hangers from the bottom of the z purlins.
INSP-Final Inspection10/30/201310/31/201310/31/2013AFAIL
DetailsTroy Cobbley
Left voice message that I would be there in 20 or 30 minutes. Arrived at job site and nobody was there. I did speak to Scott about needing to perform a rough-in inspection for the overhead system, branchline restraints and needing manufactures ok to hang piping from the bottom of the z-purlins as previously requested
INSP-Final Inspection10/25/201310/25/201310/25/2013PPART
DetailsCraig D. Hanson
final good. needs data plate and bird cage on head under stairs.
INSP-Sprinkler Rough-in/Hydro10/24/201310/24/201310/24/2013PPASS
DetailsTroy Cobbley
Above ground hydro passed
INSP-Supply line flush10/16/201310/17/201310/17/2013APASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in10/16/201310/17/201310/16/2013ACANC
DetailsTroy Cobbley
Please schedule an underground RTC. Please call Trent 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
INSP-Sprinkler Rough-in10/10/201310/11/201310/11/2013APASS
DetailsTroy Cobbley
Mezzanine piping is ok to cover.. I noted that light fixtures may block pendant heads based on flex/wiring locations next to pendants.
Sprinkler Plan Check10/10/2013 10/10/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  10/10/2013 DONE
DetailsTim Frost
Permit Ready to Issue  10/10/2013 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire10/10/2013 10/10/2013 DONE
DetailsBarbara Stitt
CHANGE STATUS TO (ISS)  10/10/2013 DONE
DetailsBarbara Stitt
(F) Reprint permit  10/10/2013 DONE
DetailsBarbara Stitt
INSP-Sprinkler Rough-in10/2/201310/3/201310/3/2013PFAIL
DetailsTroy Cobbley
Todays inspection was only for the mezzanine/office area. Resubmit plans showing the pipe routing changes to the office/mezzanine area, the use of cpvc piping and flat face bushings. No piping to be covered at this time. Also noted sprinkler main piping hangers utilizing the bottom chord of the z purlins which will need approval.
Sprinkler Plan Check9/6/2013 9/6/2013 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  9/6/2013 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  9/6/2013 DONE
DetailsTim Frost
Permit Ready to Issue  9/6/2013 DONE
Issue and Print Permit  9/6/2013 DONE
Inspection Record Card- Fire9/6/2013 9/6/2013 DONE
DetailsTisha Gallop
Plan assigned to (Tim)9/5/2013 9/5/2013 DONE
DetailsTim Frost
Application received  8/27/2013 DONE
Application submitted via PDS Online on Aug 27 2013 11:14AM