Permit Information
Permit NumberFIR13-00519
StatusFinaled
Name TYCO INTEGRATED SECURITY
Site Address 1200 N CLOVERDALE RD
Project NameCloverdale Funeral Home
Customer Number 
ePlanReviewYes
Description
Replacing the existing Edwards Panel, smoke detectors and Annunciator with a New Edwards Panel and Annuciator. The Existing Edwards Panel is Obsolete and is Failing we will be replacing the panel with a Like Panel. No associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  4/23/2014  
Case Summary  4/23/2014  
INSP-Final Inspection4/8/20144/15/20144/15/2014APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection3/26/20143/27/20143/27/2014PFAIL
DetailsTroy Cobbley
Everything is complete except the unknown signals from zone one need addressed as per the fire dept.
INSP-Final Inspection2/25/20142/26/20142/26/2014AFAIL
DetailsTroy Cobbley
Provide weather proof cover for the annunciator, repair supervisory signal on zone 6 and provide updated map showing zone 1 as a spare and zone 10 being utilized.
INSP-Final Inspection12/16/201312/19/201312/19/2013ACANC
DetailsTroy Cobbley
Cancel per art Phone #: ###-####
INSP-Final Inspection12/16/201312/18/201312/18/2013AFAIL
DetailsTroy Cobbley
NAC circuit 1 has a "open" trouble, there is only one phone line, multiple strobes are overspaced, one strobe is blocked by movable partitions, I need verification that the strobes in the prep rooms are weatherproof and the remote annunciator (located outside) is weather proof, pull station in the crematorium is mounted too high. We did not set off the strobes to check sync. or test any devices since there was a trouble on the system and only one phone line.
INSP-Final Inspection11/22/201311/25/201311/25/2013AFAIL
DetailsTroy Cobbley
No inspection and testing form, no city approved plans or notes. Strobes would not function per Art. No testing performed.
Miscellaneous action  9/30/2013 DONE
DetailsLee G Meredith
Received revised documentation. Smoke detectors will now also be replaced to meet UL compatability requirements that had previously been noted as an issue. Cross listing with the panel has been confirmed.
1st review completed  9/30/2013 PASS
DetailsLee G Meredith
Alarm Plan Check9/30/2013 9/30/2013 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/30/2013 DONE
DetailsLee G Meredith
Plans approved as noted. ProjectDox updated
Permit Ready to Issue  9/30/2013  
Inspection Record Card- Fire9/30/2013 9/30/2013 DONE
DetailsDarla L Downs
Issue and Print Permit  9/30/2013 DONE
Miscellaneous action  9/26/2013 DONE
Received proper submittal documents. In review, I noticed that the existing smoke detectors were not shown to be compatable with the new fire alarm panel that has been proposed. I emailed the applicant and requested documentation of cross listing.
Telephone call  9/26/2013 DONE
Phone call with troy Mansfield of Tyco. Discussed the requirement of cross listing of the existing detectors with the new, replacement panel. He informed me that he had been in touch with EST. They indicated that the detectors are listed with the panel and they will supply the document to him. When he receives it, they will update the case.
Miscellaneous action  9/24/2013 DONE
DetailsLee G Meredith
Emailed applicant to inform them that a fire alarm panel replacement is not allowed to be performed with a quick permit application. They will need to resubmit with the appropriate application (form 601)
Application received  9/23/2013 DONE
Application submitted via PDS Online on Sep 23 2013 5:17PM