INSP-Final Inspection | 12/3/2013 | 12/4/2013 | 12/4/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Miscellaneous action | | | 12/4/2013 | | DONE |
Lee G Meredith
|
|
|
Received electronic as built drawing from Dante. Drawing was batch stamped and acrchived in ProjectDox.
|
INSP-Final Inspection | 12/2/2013 | 12/3/2013 | 12/3/2013 | A | FAIL |
Troy Cobbley
|
|
|
Two of the four fire/smoke dampers did not operate. Also need as-builts submitted.
|
INSP-Conference | 11/26/2013 | 11/26/2013 | 11/27/2013 | P | DONE |
Troy Cobbley
|
|
|
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian A
|
Miscellaneous action | | | 10/1/2013 | | DONE |
|
|
|
No response on email regarding my question of why the designated door release smoke detectors don't trigger building notification and alarm to central station. I redlined this on the the matrix to confirm the operation nopted properly.
|
1st review completed | | | 10/1/2013 | | PASS |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 10/1/2013 | | 10/1/2013 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/1/2013 | | DONE |
Lee G Meredith
|
|
|
Plans approved as noted. ProjectDox updated
|
Permit Ready to Issue | | | 10/1/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 10/1/2013 | | 10/1/2013 | | DONE |
Darla L Downs
|
|
|
|
Issue and Print Permit | | | 10/1/2013 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 9/30/2013 | | 9/30/2013 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 9/30/2013 | | DONE |
Lee G Meredith
|
|
|
Emaile Dante for clarification. Matrix indicates that the “Designated Door Release Smoke Detectors” do not activate notification appliances or transmit an alarm to central station. Is this a typo or is there some other reason these act as stand-alone detectors?
|
Application received | | | 9/27/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 27 2013 4:07PM
|