Permit Information
Permit NumberFIR13-00535
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1055 N CURTIS RD
Project NameSARMC Temporary Exam
Customer Number 
ePlanReviewYes
Description
Temporary Exam TI is to add 3 ceiling strobes and 4 in-duct detectors. Existing FA system in the building to tie into. This TI is part of the ED department. Associated building permit: BLD13-01947
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/3/201312/4/201312/4/2013PPASS
DetailsTroy Cobbley
Permit finaled
Miscellaneous action  12/4/2013 DONE
DetailsLee G Meredith
Received electronic as built drawing from Dante. Drawing was batch stamped and acrchived in ProjectDox.
INSP-Final Inspection12/2/201312/3/201312/3/2013AFAIL
DetailsTroy Cobbley
Two of the four fire/smoke dampers did not operate. Also need as-builts submitted.
INSP-Conference11/26/201311/26/201311/27/2013PDONE
DetailsTroy Cobbley
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian A
Miscellaneous action  10/1/2013 DONE
No response on email regarding my question of why the designated door release smoke detectors don't trigger building notification and alarm to central station. I redlined this on the the matrix to confirm the operation nopted properly.
1st review completed  10/1/2013 PASS
DetailsLee G Meredith
Alarm Plan Check10/1/2013 10/1/2013 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/1/2013 DONE
DetailsLee G Meredith
Plans approved as noted. ProjectDox updated
Permit Ready to Issue  10/1/2013  
Inspection Record Card- Fire10/1/2013 10/1/2013 DONE
DetailsDarla L Downs
Issue and Print Permit  10/1/2013 DONE
Plan assigned to (Lee)9/30/2013 9/30/2013 DONE
DetailsLee G Meredith
Miscellaneous action  9/30/2013 DONE
DetailsLee G Meredith
Emaile Dante for clarification. Matrix indicates that the “Designated Door Release Smoke Detectors” do not activate notification appliances or transmit an alarm to central station. Is this a typo or is there some other reason these act as stand-alone detectors?
Application received  9/27/2013 DONE
Application submitted via PDS Online on Sep 27 2013 4:07PM