INSP-Final Inspection | 1/25/2019 | 1/31/2019 | 1/31/2019 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection for area of work complete.
Ray McQueen, inspecting technician, ###-####, 7:00am start time please Phone #: ###-#### Inspection requested via web by Rose Peterson
|
INSP-Final Inspection | 1/24/2019 | 1/25/2019 | 1/25/2019 | A | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact.
Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
|
INSP-Final Inspection | 12/28/2018 | 1/4/2019 | 1/2/2019 | A | CANC |
Troy Cobbley
|
|
|
Ray McQueen, inspecting technician Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|
Issue and Print Permit | | | 12/4/2018 | | DONE |
|
|
|
|
Alarm Plan Check | 12/3/2018 | | 12/3/2018 | | PASS |
Lee G Meredith
|
|
|
Plans passed as noted.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/3/2018 | | DONE |
|
|
|
Plans passed as noted. As built drawings and calcs. required.
|
Permit Ready to Issue | | | 12/3/2018 | | DONE |
|
|
|
PLAN MOD NO FEE PER LEE
|
Intake Approval | | | 12/3/2018 | | PASS |
|
|
|
left message for branch manager that this permit is ready to be picked up
|
Plan resubmittals received | | | 9/11/2018 | | DONE |
|
|
|
Three copies of sheets FA-1 and FA-2 taken to Lee
|
INSP-Final Inspection | 5/14/2018 | 5/15/2018 | 5/15/2018 | P | CANC |
Jim Page
|
|
|
Ray McQueen, inspecting technician. Building is open access Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|
INSP-Final Inspection | 5/11/2018 | 5/18/2018 | 5/14/2018 | P | CANC |
Troy Cobbley
|
|
|
Ray McQueen, inspecting technician, building has open access Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|
Miscellaneous action | | | 8/22/2017 | | DONE |
|
|
|
Emailed Rose Peterson requesting work completion so the project can be closed. Rose responded to say they would have it complete by the end of the year.
|
FIR-Aging Inspection | 7/25/2017 | 7/25/2017 | 7/25/2017 | | NR |
Troy Cobbley
|
|
|
Per Rose this work should be completed next month and a final inspection scheduled
|
Miscellaneous action | | | 2/14/2017 | | DONE |
|
|
|
Emailed Rose to request completion of the project and final acceptance test.
|
INSP-Final Inspection | 9/4/2014 | 9/4/2014 | 9/5/2014 | P | FAIL |
Forrest France
|
|
|
Completed initial project walkthrough. Items noted include; a plan modification will be required due to deletion of elevator recall functions (SD's and HD's), floor plan changes, addition of two MP stations, and changes in notification circuts. Need to provide missing coverage at conference rooms and common areas, post sign at the door to the FACP room, cd settings need adjusted at some locations, spacing and coverage need modified as noted. Plans to match field installation. Provide confirmation from the state elevator division regarding elevator recall.
|
Issue and Print Permit | | | 12/3/2013 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 10/4/2013 | | 12/2/2013 | | DONE |
|
|
|
|
Alarm Plan Check | 12/2/2013 | | 12/2/2013 | | PASS |
Lee G Meredith
|
|
|
Plans approved. Comments attached.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/2/2013 | | DONE |
Lee G Meredith
|
|
|
Approved drawings & comments taken to front desk for processing.
|
Telephone call | | | 12/2/2013 | | DONE |
Lee G Meredith
|
|
|
Ceiling height not indicated on resubmittal. I called Brett Anderson. He confirmed that all ceilings are less than 10 feet in height.
|
Permit Ready to Issue | | | 12/2/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 12/2/2013 | | 12/2/2013 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 12/2/2013 | | |
|
|
|
called Brett and told him permit is ready and fee
|
Plan resubmittals received | | | 11/29/2013 | | DONE |
|
|
|
|
Telephone call | | | 10/8/2013 | | DONE |
Lee G Meredith
|
|
|
REceived a call frim Brett Andersen requesting further detail on my review comment requesting room desctiptions.. I told him that the basement showed visual notification for all rooms except for 2 that weren't labeled for their use. Without room definition, I was not able to determine why visuals weren't included for these rooms. He said that he understood and would visit the site to get the information for the resubmittal.
|
1st review completed | | | 10/7/2013 | | FAIL |
Lee G Meredith
|
|
|
Failed review. See drawing red line notes and review comments.
|
Telephone call | | | 10/7/2013 | | DONE |
Tisha Gallop
|
|
|
called Bret at Mountain Alarm and told him denied plans at front desk.
|
Application received | | | 10/4/2013 | | DONE |
|
|
|
|