INSP-Final Inspection | 8/4/2014 | 8/5/2014 | 8/5/2014 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 7/25/2014 | 7/28/2014 | 7/28/2014 | A | FAIL |
Craig D. Hanson
|
|
|
Ssytm did not function properly, pre-sction devices not triping fire sprinkler.
|
INSP-Sprinkler Rough-in | 6/5/2014 | 6/6/2014 | 6/6/2014 | P | PASS |
Troy Cobbley
|
|
|
24 hour air test on Coolers passed
|
INSP-Sprinkler Rough-in | 6/4/2014 | 6/5/2014 | 6/5/2014 | A | PASS |
Troy Cobbley
|
|
|
Finished the 24 hour air test (passed) on the freezers at 7:15am this morning and began the 24 hour air test on the coolers at 1:00pm this afternoon
|
INSP-Sprinkler Rough-in | 6/3/2014 | 6/4/2014 | 6/4/2014 | A | PASS |
Troy Cobbley
|
|
|
24 hour air test started at 7:30 with 42psi on the guage. Piping in the racks and the freezer area passed. Branchline restraints are required to be installed in the freezer area.
|
Sprinkler Plan Check | 5/12/2014 | | 5/12/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/12/2014 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 5/12/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Issue and Print Permit | | | 5/12/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 5/12/2014 | | 5/12/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Miscellaneous action | | | 4/18/2014 | | PEND |
|
|
|
The drawings and documents are ok. However, they cannot be approved since a releasing/detection system has not been submitted.
|
Sprinkler Plan Check | 12/2/2013 | | 12/2/2013 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 12/2/2013 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 12/2/2013 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Plan assigned to (Tim) | 10/16/2013 | | 10/16/2013 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 10/16/2013 | | 10/16/2013 | | FAIL |
Tim Frost
|
|
|
Prescreen Review
|
Application received | | | 10/10/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 10 2013 7:21AM
|