Case Summary | | | 2/18/2016 | | DONE |
|
|
|
|
Case Summary | | | 2/4/2014 | | |
|
|
|
|
INSP-Final Inspection | 10/21/2013 | 10/22/2013 | 10/22/2013 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/18/2013 | 10/21/2013 | 10/21/2013 | A | FAIL |
Troy Cobbley
|
|
|
All items ok except the strobes do not flash as required per NFPA 72 18.5.2.1 (There was a timeed three second delay between some flashes)
|
Issue and Print Permit | | | 10/17/2013 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 10/14/2013 | | 10/16/2013 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 10/16/2013 | | DONE |
|
|
|
Received email from Mary Froemke stating that clear was accepatble with Chris Morrow of Sonitorol.
|
1st review completed | | | 10/16/2013 | | PASS |
Lee G Meredith
|
|
|
Revised amber strobes to clear.
|
Alarm Plan Check | 10/16/2013 | | 10/16/2013 | | PASS |
Lee G Meredith
|
|
|
Plans approved with red line comments on drawings and documents.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/16/2013 | | DONE |
Lee G Meredith
|
|
|
Approved plans taken to front desk for processing.
|
Telephone call | | | 10/16/2013 | | DONE |
Christina Prado
|
|
|
Called Chris to advise permit is ready and gave fees due
|
Permit Ready to Issue | | | 10/16/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 10/16/2013 | | 10/16/2013 | | DONE |
Christina Prado
|
|
|
|
Miscellaneous action | | | 10/15/2013 | | DONE |
Lee G Meredith
|
|
|
Mary Fromke emailed a link to a web page that indicated the product was for ceiling mount but did not include a product data sheet. I found the correct product sheet (amber in color) and emailed it to her with the one that will be required (clear). She indicated that she will forward the information and requirement for clear strobes on to the customer.
|
Application received | | | 10/14/2013 | | |
|
|
|
|
Telephone call | | | 10/14/2013 | | DONE |
Lee G Meredith
|
|
|
Called Chris Morror of Sonitrol to clarify why an amber colored strobe was submitted. He informed me that they have several throughout the facility and would like to continue. Current sequence of operations does not seperate amber (emergency condition) from clear (fire alarm condition) so clear will be required since this device is for fire alarm. Also, I informed him that the product submitted stated that it was for wall mount but design indicated ceiling mount. I informed him that I would requrie the proper product data sheet.
|