Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR13-00567
StatusFinaled
Name SONITROL PACIFIC
Site Address 7500 W MOSSY CUP ST
Project NameNxEdge Boise Operations T.I.
Customer Number 
ePlanReviewNo
Description
Add 2 clear horn / strobes (existing in clean room are amber) to new rooms created by remodel. Associated building permit: BLD13-01527.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  2/18/2016 DONE
Case Summary  2/4/2014  
INSP-Final Inspection10/21/201310/22/201310/22/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/18/201310/21/201310/21/2013AFAIL
DetailsTroy Cobbley
All items ok except the strobes do not flash as required per NFPA 72 18.5.2.1 (There was a timeed three second delay between some flashes)
Issue and Print Permit  10/17/2013 DONE
Plan assigned to (Lee)10/14/2013 10/16/2013 DONE
DetailsLee G Meredith
Miscellaneous action  10/16/2013 DONE
Received email from Mary Froemke stating that clear was accepatble with Chris Morrow of Sonitorol.
1st review completed  10/16/2013 PASS
DetailsLee G Meredith
Revised amber strobes to clear.
Alarm Plan Check10/16/2013 10/16/2013 PASS
DetailsLee G Meredith
Plans approved with red line comments on drawings and documents.
PLANS TAKEN FRONT DESK ALARM  10/16/2013 DONE
DetailsLee G Meredith
Approved plans taken to front desk for processing.
Telephone call  10/16/2013 DONE
DetailsChristina Prado
Called Chris to advise permit is ready and gave fees due
Permit Ready to Issue  10/16/2013 DONE
DetailsChristina Prado
Inspection Record Card- Fire10/16/2013 10/16/2013 DONE
DetailsChristina Prado
Miscellaneous action  10/15/2013 DONE
DetailsLee G Meredith
Mary Fromke emailed a link to a web page that indicated the product was for ceiling mount but did not include a product data sheet. I found the correct product sheet (amber in color) and emailed it to her with the one that will be required (clear). She indicated that she will forward the information and requirement for clear strobes on to the customer.
Application received  10/14/2013  
Telephone call  10/14/2013 DONE
DetailsLee G Meredith
Called Chris Morror of Sonitrol to clarify why an amber colored strobe was submitted. He informed me that they have several throughout the facility and would like to continue. Current sequence of operations does not seperate amber (emergency condition) from clear (fire alarm condition) so clear will be required since this device is for fire alarm. Also, I informed him that the product submitted stated that it was for wall mount but design indicated ceiling mount. I informed him that I would requrie the proper product data sheet.