Permit Information
Permit NumberFIR13-00612
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 12600 W USTICK RD
Project NameUstick Apartments
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of 8 unit apartment protected with a NFPA 13R system. A 2” dedicated supply is being brought into a riser room with (2) floor level control valves. The riser is 1½” with a 1½” FDC and backflow preventer.
Bldg 1: To construct a new 6,312 square feet, three story, eight unit, apartment building and associated site work per plans. Each unit shares a common path of egress into and through a 1-hour exterior exit enclosure with 60-minute fire-resistive, listed, labeled, self-closing door assemblies from the dwelling units into the exit enclosure. All 1st floor units are required to comply as Type 'B' accessible dwelling units. All construction shall be per the approved plans, engineering, and attached plan review report. NOTE: This building is required to be fully fire sprinklered per NFPA 13R. CUP12-00040 and DRH12-00187 per Planning and Zoning. **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/8/20155/11/20155/11/2015PPASS
DetailsTroy Cobbley
Permit finaled. FDC relocated, with fire dept approval, to the north side parking lot access.
INSP-Final Inspection4/20/20154/22/20154/22/2015PFAIL
DetailsTroy Cobbley
Inspected tamper switch interconnection with the FACP but could not do much else do to the painter starting to paint (multiple heads have been replaced due to paint), correct orfice not installed on the inspectors test and the outside alarm bell has been installed at the riser room not at the FDC which is on the other side of the building. Also I'm going to contact the fire dept about the FDC placement due to a fence being installed between the FDC and the street.
INSP-Final Inspection4/17/20154/20/20154/20/2015PCANC
DetailsTroy Cobbley
Cancel per Robert
INSP-Final Inspection3/11/20153/12/20153/12/2015AFAIL
DetailsTroy Cobbley
I left message on contacts phone that I was on the way. Arrived at job site. No one was there and all apartments locked. Project related fire alarm permit has not been scheduled and the FACP is not powered up. No inspection was performed.
INSP-Sprinkler Rough-in/Hydro8/5/20148/5/20148/5/2014PPASS
DetailsTroy Cobbley
Overhead hydro tests passed. Rough-in passed. Piping can be covered.
INSP-Sprinkler Rough-in/Hydro8/4/20148/4/20148/4/2014PFAIL
DetailsTroy Cobbley
Overhead hydro tests failed due to visable leakage at multiple pendant heads. Also two pendant heads deflectors have been damaged.
INSP-Sprinkler Rough-in/Hydro7/31/20148/1/20148/1/2014PCANC
DetailsTroy Cobbley
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in/Hydro7/30/20147/31/20147/31/2014ACANC
DetailsTroy Cobbley
Cancel per Robert due to damaged piping
INSP-Supply line flush7/29/20147/30/20147/30/2014APASS
DetailsTroy Cobbley
Supply line flush passed
INSP-Sprinkler Rough-in/Hydro7/25/20147/29/20147/29/2014ACANC
DetailsTroy Cobbley
Cancel per Robert
Miscellaneous action  7/29/2014 DONE
The designer had already factor in the correct amount of underground piping therefore only As Built drawing were required, a Plan Mod was not necessary.
INSP-Supply line flush7/25/20147/28/20147/28/2014AFAIL
DetailsCraig D. Hanson
System is not installed per plan. Plan Mod may be needed.
INSP-Sprinkler Rough-in7/25/20147/28/20147/28/2014APASS
DetailsCraig D. Hanson
Ok to cover. flush still needs to be done.
INSP-Sprinkler Rough-in7/25/20147/25/20147/25/2014PCANC
DetailsTroy Cobbley
No approved plans on site so Robert is going to reschedule for monday with a flush.
INSP-Supply line flush7/25/20147/28/20147/25/2014ACANC
DetailsTroy Cobbley
This is an ug to cover. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in1/14/20141/15/20141/15/2014AFAIL
DetailsTroy Cobbley
Piping as installed is ok except for an overspaced pendant and a blocked pendant. Plans need to be resubmitted due to extensive pipe re-routing and additional fittings in the supply piping which will effect the hydraulic calculations. No tenting has been performed/installed yet. No cover of piping is allowed yet.
INSP-Sprinkler Rough-in/Hydro1/14/20141/15/20141/14/2014ACANC
DetailsTroy Cobbley
Please call 45 min prior to inspection. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
Permit Ready to Issue  12/12/2013 DONE
DetailsChristina Prado
Issue and Print Permit  12/12/2013 DONE
DetailsChristina Prado
Inspection Record Card- Fire12/12/2013 12/12/2013 DONE
DetailsChristina Prado
Sprinkler Plan Check12/11/2013 12/11/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  12/11/2013 DONE
DetailsTim Frost
Sprinkler Plan Check12/6/2013 12/6/2013 FAIL
DetailsTim Frost
1st review completed  12/6/2013 FAIL
DetailsTim Frost
Plan assigned to (Tim)12/5/2013 12/5/2013 DONE
DetailsTim Frost
Application received  11/4/2013 DONE
Application submitted via PDS Online on Nov 4 2013 2:41PM