Permit Information
Permit NumberFIR13-00618
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 423 N MITCHELL ST
Project NameRSD Warehouse
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of providing a new wet system for an office warehouse. The warehouse area is divided into two tenants. A new 6” C-900 underground main will supply the system. There is a 6 header equipped with a 6” backflow preventer and 6” riser manifold. The warehouse area is design as a 4”x3”x2” grid. The mercantile/office area is supply by the primary main with a side feed type system. ELO sprinklers are being utilized in the warehouse area.

Refrigeration Supplies Distributor - Tenant Improvement - To finish an approximately 21,000 square foot tenant space within a new 25,900 square foot shell building. The new tenant space will be located on the east side of the new shell building and will include a showroom, part supply, offices, training room, and warehouse space for Refrigeration Supplies Distributor (Tenant A). This permit also includes related interior fit & finish, mechanical, electrical & plumbing as required for a finished tenant space
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/29/20145/30/20145/30/2014APASS
DetailsTroy Cobbley
Permit finaled
Miscellaneous action  5/30/2014 PASS
Reviewed as built drawings. Everything was ok but the column protection needs to be installed at 15' not the 12' shown on the drawing.
INSP-Final Inspection5/21/20145/22/20145/22/2014PFAIL
DetailsTroy Cobbley
Provide re-submittals as previously discussed. Forward flush passed and final rough-in inspection for the office area passed.
INSP-Sprinkler Rough-in/Hydro4/21/20144/22/20144/22/2014APASS
DetailsTroy Cobbley
Overhead hydro test passed.
INSP-Sprinkler Rough-in3/25/20143/27/20143/27/2014PPASS
DetailsTroy Cobbley
Overhead rough-in passed. Will need a cover inspection once the pendant heads in the office area are installed. It appears that branchline restraints will be required and the combustible concealed space at the front entrance will need addressed. Mike stated that they are resubmitting showing the column protection and the relocation of the east main (office area).
Sprinkler Plan Check3/24/2014 3/24/2014 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  3/24/2014 DONE
DetailsTim Frost
CHANGE STATUS TO (ISS)  3/24/2014 DONE
plan mod approved and paid
INSP-Supply line flush3/20/20143/21/20143/21/2014PPART
DetailsForrest France
UG fire supply line flush completed satisfactory.
INSP-Sprinkler Rough-in/Hydro3/14/20143/14/20143/14/2014PPASS
DetailsTroy Cobbley
The ug hydro passed
INSP-Sprinkler Rough-in2/21/20142/24/20142/25/2014PPART
DetailsForrest France
UG fire supply line including the IBR approved for bury.
Permit Ready to Issue  12/26/2013 DONE
DetailsChristina Prado
Issue and Print Permit  12/26/2013 DONE
DetailsChristina Prado
Inspection Record Card- Fire12/26/2013 12/26/2013 DONE
DetailsChristina Prado
Sprinkler Plan Check12/23/2013 12/23/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  12/23/2013 DONE
DetailsTim Frost
Sprinkler Plan Check12/9/2013 12/9/2013 FAIL
DetailsTim Frost
1st review completed  12/9/2013 FAIL
DetailsTim Frost
Miscellaneous action  12/9/2013 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Miscellaneous action  12/6/2013 DONE
Sent the following email to Tom

Tom,

Some of the items were not corrected in the orignal prescreen review.

Additionally,
The owner's certificate provided by Tim Haymes indicates 5-10 pallet loads of f;ammable and combustible liquids, aerosol, compressed gas, and oxiders. The warehouse is obviously capable of storing more than 10 pallet loads. Based on the owner's certificate you originally provided I see a great deal of plastics. At this time I am not convinced this is a class IV warehouse. Please, complete form 606 for each commodity. NOTE: Where it says commodity description provide the commodity and packaging description NOT the commodity classification. The flammable liquids and the other hazardous materials are in small enough quantities they do not appear to cause a problem. However, per IFC 2304.1 the system has to be designed for the worst hazard. Tim Haymes has supplied be with a list of the high hazard materials. What is the remainder being stored? How/Why are you designing for a Class IV? I need more information on the material being stored and the packaging material.

Tim
Miscellaneous action  11/19/2013 DONE
Sent the following email to Tom Easton

Tom,

I need an accurately completed Owner’s Certificate (please see attached). I need and accurately completed HMI (Hazardous Material Inventory Statement). I require exact quantities (do not use the words small medium large, etc.) see IFC 407.5, 2701.5.2 Please, complete all items in 2701.5.2 for EACH hazardous material. I have circled a few of the hazardous materials I noticed. I have also enclosed a list of City of Boise approved HMI consultants. There may not be a large enough quantity of a material to pose a problem. However, combined they may be a problem. Until we have exact quantities there is no way to know for certain.

Where is the Idle Pallets being stored (how high)?

Looking over the list of materials, I find it highly dubious the materials contain <25% plastics. Please, verify.

Due to several situations, now and in the future, I require that the Owner’s Certificate be completed by owner, NOT and owner’s representative.

This project will be on hold until I received the above information.
Plan assigned to (Tim)11/13/2013 11/13/2013 DONE
DetailsTim Frost
Plan assigned to (Tim)11/13/2013 11/13/2013 FAIL
DetailsTim Frost
Failed prescreen
Application received  11/6/2013 DONE
Application submitted via PDS Online on Nov 6 2013 9:13AM