INSP-Final Inspection | 4/15/2014 | 4/15/2014 | 4/15/2014 | P | PASS |
Forrest France
|
|
|
Verified completion of previous inspection notes. Fire alarm permit finaled.
|
INSP-Final Inspection | 3/12/2014 | 3/18/2014 | 3/18/2014 | P | PART |
Forrest France
|
|
|
Completed fire alarm acceptance testing. Necessary adjustments made while on site. Scope of work completed. Final pending installation of a knox box per review note item #13.
|
INSP-Final Inspection | 3/7/2014 | 3/7/2014 | 3/7/2014 | P | NH |
Forrest France
|
|
|
|
Issue and Print Permit | | | 12/9/2013 | | DONE |
|
|
|
|
Miscellaneous action | | | 11/15/2013 | | DONE |
Lee G Meredith
|
|
|
Corrected typo on fire plan review comments. Referenced permit was showing as FIR13-00606. Corrected to FIR13-00648. Uploaded revised review comments to Tidemark documents.
|
Plan assigned to (Lee) | 11/13/2013 | | 11/14/2013 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 11/14/2013 | | PASS |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 11/14/2013 | | 11/14/2013 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/14/2013 | | DONE |
Lee G Meredith
|
|
|
Approved plans with comments taken to front desk for processing.
|
Permit Ready to Issue | | | 11/14/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 11/14/2013 | | 11/14/2013 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 11/14/2013 | | DONE |
Christina Prado
|
|
|
called Tim to advise permit is ready and gave fees due
|
Application received | | | 11/13/2013 | | |
|
|
|
|