Case Summary | | | 4/4/2014 | | |
|
|
|
|
INSP-Final Inspection | 12/19/2013 | 12/20/2013 | 12/20/2013 | P | PASS |
Forrest France
|
|
|
Fire alarm permit work passed inspection and testing.
|
Permit Ready to Issue | | | 11/22/2013 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 11/22/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 11/22/2013 | | 11/22/2013 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 11/22/2013 | | DONE |
Lee G Meredith
|
|
|
Rob Ahten called to discuss the requirement of remote alarm indiactors on duct smokes, as noted on the review comments. I agreed that they will not be required as long as the fire alarm panel indicates which specific duct smoke is active per 2010 NFPA 72 17.4.9.
|
Plan assigned to (Lee) | 11/21/2013 | | 11/21/2013 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 11/21/2013 | | PASS |
Lee G Meredith
|
|
|
Review passed with notation on drawing.
|
Alarm Plan Check | 11/21/2013 | | 11/21/2013 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/21/2013 | | DONE |
Lee G Meredith
|
|
|
Plans approved with comments and red line drawing notation. ProjectDox updated.
|
Application received | | | 11/19/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 19 2013 9:42AM
|