INSP-Final Inspection | 2/20/2014 | 2/21/2014 | 2/21/2014 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 2/18/2014 | 2/19/2014 | 2/19/2014 | P | PART |
Forrest France
|
|
|
Final pending project related fire alarm permit work.
|
Sprinkler Plan Check | 2/19/2014 | | 2/19/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 2/19/2014 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/19/2014 | | DONE |
Tim Frost
|
|
|
|
CHANGE STATUS TO (ISS) | | | 2/19/2014 | | DONE |
Tisha Gallop
|
|
|
no fee for plan mod per Tim Frost
|
INSP-Sprinkler Rough-in/Hydro | 2/13/2014 | 2/14/2014 | 2/14/2014 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic testing for both wet systems passed. Need to provide 1st floor office area plans, missing flexible couplings at the base of the risers.
|
Sprinkler Plan Check | 2/13/2014 | | 2/13/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/13/2014 | | DONE |
Tim Frost
|
|
|
|
Issue and Print Permit | | | 2/13/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/13/2014 | | 2/13/2014 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (Tim) | 2/10/2014 | | 2/13/2014 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 2/11/2014 | | 2/11/2014 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 2/11/2014 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Sprinkler Plan Check | 1/17/2014 | | 1/17/2014 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 1/17/2014 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Early Start | | | 1/15/2014 | | PASS |
|
|
|
|
Sprinkler Plan Check | 11/25/2013 | | 11/25/2013 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 11/25/2013 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 11/25/2013 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Plan assigned to (Tim) | 11/22/2013 | | 11/22/2013 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 11/21/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 21 2013 1:42PM
|