INSP-Alarm Testing | 9/11/2018 | 9/11/2018 | 9/11/2018 | P | PASS |
Lee G Meredith
|
|
|
Tested elevator shunt power monitoring and flashing firemans hat in elevator. Waiting for as built drawings and record of completion.
|
DOC - Permit Finaled | | | 9/11/2018 | | DONE |
|
|
|
System passed inspection all required documents provided.
|
INSP-Final Inspection | 9/10/2018 | 9/11/2018 | 9/10/2018 | P | CANC |
Jim Page
|
|
|
Building access is open, inspection technician is Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|
INSP-Final Inspection | 1/2/2018 | 1/3/2018 | 1/3/2018 | A | CANC |
Troy Cobbley
|
|
|
Ray McQueen will be the technician. ###-####. Building access 8-5. Phone #: ###-#### Inspection requested via web by Rose Peterson
|
INSP-Final Inspection | 12/18/2017 | 12/18/2017 | 12/18/2017 | P | CANC |
Jim Page
|
|
|
Technician is Ray McQueen. Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|
Miscellaneous action | | | 8/22/2017 | | DONE |
|
|
|
Sent Rose a request to complete this work so it can be closed. Rose responded to say they would have it complete by the end of the year.
|
Telephone call | | | 7/15/2014 | | DONE |
|
|
|
The property manager from Select Commercial called to discuss the requirements of elevator shunt trip power monitoring. I informed him that if there is a shunt trip feature that the power is required to be monitoried. I explained the reasoning behind the requirement and told him that his fire alarm contractor should be able to accomplish this.
|
INSP-Final Inspection | 6/24/2014 | 7/1/2014 | 7/1/2014 | A | FAIL |
Troy Cobbley
|
|
|
Need as-builts, need the 120 vac for the elevator monitored and the machine room smoke detector did not cause a flashing hat in the elevator car.
|
INSP-Final Inspection | 5/16/2014 | 5/20/2014 | 5/20/2014 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for locations and types of corrections needed. They include the need for addirional audio/visual devices and atleast one new smoke detector. Several wall mounted smoke detectors need relocated closer to the ceiling. As-builts are needed as well as the testing of the elevator recall, EOL's and fire sprinkler devices.
|
INSP-Conference | 3/24/2014 | 3/25/2014 | 4/4/2014 | A | DONE |
Forrest France
|
|
|
Ray McQueen Phone #: ###-####
|
INSP-Conference | 3/20/2014 | 3/21/2014 | 3/21/2014 | A | DEFR |
Forrest France
|
|
|
ray Phone #: ###-####
|
Issue and Print Permit | | | 1/22/2014 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 12/3/2013 | | 1/21/2014 | | DONE |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 1/21/2014 | | 1/21/2014 | | PASS |
Lee G Meredith
|
|
|
Plans approved with comments and red line notation.
|
PLANS TAKEN FRONT DESK ALARM | | | 1/21/2014 | | DONE |
|
|
|
Plans approved with comments and red line notation.
|
Permit Ready to Issue | | | 1/21/2014 | | |
|
|
|
|
Inspection Record Card- Fire | 1/21/2014 | | 1/21/2014 | | DONE |
Darla L Downs
|
|
|
|
Telephone call | | | 1/21/2014 | | |
|
|
|
1-21-14 called Brett Anderson permit ready and fee given ///dld
|
Plan resubmittals received | | | 1/17/2014 | | DONE |
Tisha Gallop
|
|
|
received two copies; routed to LGM
|
1st review completed | | | 12/5/2013 | | FAIL |
Lee G Meredith
|
|
|
1st review failed. See review comments and drawing red lines.
|
Miscellaneous action | | | 12/5/2013 | | DONE |
Lee G Meredith
|
|
|
Emailed review comments to applicant.
|
Application received | | | 12/3/2013 | | |
|
|
|
|