INSP-Final Inspection | 7/18/2014 | 7/18/2014 | 7/18/2014 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 4/7/2014 | 4/7/2014 | 4/7/2014 | P | PART |
Forrest France
|
|
|
Okay to cover overhead work at the Tri-classroom and the monitor room as marked and dated on stamped plans.
|
INSP-Sprinkler Rough-in | 1/9/2014 | 1/10/2014 | 1/10/2014 | A | PASS |
Troy Cobbley
|
|
|
Pendant head locations in relation to the duct work have been modified and are acceptable. Piping can be covered.
|
INSP-Sprinkler Rough-in | 1/8/2014 | 1/9/2014 | 1/9/2014 | A | PART |
Troy Cobbley
|
|
|
Piping installation passed but round duct work installed below the ceiling is causing obstructions. Don and I went over the "three times rule" in NFPA 13. He is going to modify the installation.
|
Override - Parcel Holds | 1/8/2014 | 1/1/1900 | 1/8/2014 | | |
|
|
|
fir inspection
|
Plan assigned to (Tim) | 12/20/2013 | | 12/20/2013 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 12/20/2013 | | 12/20/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 12/20/2013 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/20/2013 | | DONE |
Tim Frost
|
|
|
|
Override - Parcel Holds | | | 12/20/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 12/20/2013 | | 12/20/2013 | | DONE |
Barbara Stitt
|
|
|
|
Override - Parcel Holds | | | 12/20/2013 | | |
|
|
|
|
Issue and Print Permit | | | 12/20/2013 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 12/19/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 19 2013 11:52AM
|