INSP-Final Inspection | 3/26/2014 | 3/27/2014 | 3/27/2014 | A | PASS |
Forrest France
|
|
|
C/N items verified for completion. Acceptance testing passed. Fire alarm permit finaled.
|
INSP-Final Inspection | 3/24/2014 | 3/25/2014 | 3/25/2014 | A | NR |
Forrest France
|
|
|
Noted correction items include; cd setting at one classroom, two overspaced av's at entry vestibules, missing coverage at the womens restroom vestibule, provide relay to mag lock at the SE exit door, post points map, need record of inspection and testing forms, missing knox box.
|
Fees Due Hold | 2/8/2014 | | 3/12/2014 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 2/7/2014 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 2/7/2014 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 2/7/2014 | | 2/7/2014 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (Lee) | 2/6/2014 | | 2/6/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 2/6/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 2/6/2014 | | 2/6/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 2/6/2014 | | DONE |
|
|
|
Plans approved with comments and red line notes on drawings. ProjectDox updated.
|
Application received | | | 2/5/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 5 2014 2:13PM
|