Permit NumberFIR14-00127
StatusVoid/No Violation
Name AUDIO ELECTRONICS INC
Site Address 2509 S BROADWAY AVE
Project NameOffice Max FA System Remod
Customer Number 
ePlanReviewYes
Description
The existing system does not have any supervised circuits (IDC or NAC). FACP is to be relocated from above the ceiling, to an accessible space, and the smoke detector will be relocated to above the FACP. The Remote annunciator will be relocated to the front entry. Open air splices will be enclosed.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permit VOIDED9/18/20189/18/20189/18/2018 DONE
DetailsRita DeYoung
Per David Oliver
Miscellaneous action  9/18/2018 DONE
Emailed Dave Oliver and requested AEI schedule an acceptance test. He inicated the owner canceled the work. Told him to void the permit.
Miscellaneous action  11/3/2014 DONE
Emailed Jason Minnick requesting an update. Owner has not moved forward on code upgrade requirements.
Telephone call  9/5/2014 DONE
Jason Minnick called to say that the wonew has agreed to replace the existing fire alarm panel and bring the entire fire alarm system up to current code. He will resubmit under the same permit number with a full permit to replace the original quick permit.
Telephone call  9/4/2014 DONE
Jason Minnick called to discuss what would be required to complete the project. At the time of construction (1996) The UFC did not require notification so Jason asked if the notification could be removed. After research with Scott Arellano, it was determined that the reason the building had notification is due to the Americans with Disibilities Act (ADA). I informed Jason of this and that full compliance with 1996 NFPA 72 installation requirements and ADA guidelines will be required but I recommended meeting current code due to the age of the existing fire alarm panel. I followed the phone conversation with a recap of our discussion via email.
INSP-Final Inspection8/28/20149/3/20149/3/2014AFAIL
DetailsTroy Cobbley
NFPA "Testing and Inspeciton" form and "signal test reports not provided. Heights of notification devices have been modified. NAC/Power Supplies have been provided for each of the two notification circuits. Neither one of these items is shown on the plans. Per conversation with plan review notification shall be provided through-out as per NFPA 72. I noted that the north side of the building strobes flash about once every second. The south side strobes flash once every six seconds and the horn tone is "solid tone". It appears that none of the NAC or IDC curcuits are supervised. We tested the smoke detector at the FACP and a manual pull station which registered correctly at the remote annunciator. Plans need to be submitted showing all devices utilized, correct scope of work and actual field conditions/function of the fire alarm system. See NFPA 72; (18.4.2 temporal), (18.5.3.1 strobe flash rate), (10.8.2.3 supervision/trouble signals)
Permit Ready to Issue  3/10/2014 DONE
DetailsChristina Prado
Issue and Print Permit  3/10/2014 DONE
DetailsChristina Prado
Inspection Record Card- Fire3/10/2014 3/10/2014 DONE
DetailsChristina Prado
Plan assigned to (Lee)3/7/2014 3/7/2014 DONE
DetailsLee G Meredith
1st review completed  3/7/2014 PASS
Alarm Plan Check3/7/2014 3/7/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/7/2014 DONE
Plans approved. Projectdox updated.
Application received  3/5/2014 DONE
Application submitted via PDS Online on Mar 5 2014 2:57PM