Case Summary | | | 2/2/2015 | | |
|
|
|
|
INSP-Final Inspection | 6/20/2014 | 6/23/2014 | 6/23/2014 | P | PASS |
Forrest France
|
|
|
Verified previous correction notice items. Fire alarm permit finaled.
|
INSP-Final Inspection | 6/4/2014 | 6/4/2014 | 6/4/2014 | P | FAIL |
Troy Cobbley
|
|
|
All devices tested ok but a 117cd strobe needs to be added in the ADA room or the 110cd strobe needs to be lowered to less than 24"
|
INSP-Alarm Testing | 5/27/2014 | 5/27/2014 | 5/27/2014 | A | PEND |
Forrest France
|
|
|
|
INSP-Final Inspection | 5/12/2014 | 5/16/2014 | 5/16/2014 | A | FAIL |
Troy Cobbley
|
|
|
Weather proof back boxes have not been installed as per the approved plans. Also room 119/ADA room was still occupied. No actual testing was performed.
|
CHANGE STATUS TO (ISS) | | | 5/9/2014 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (Lee) | 3/21/2014 | | 3/24/2014 | | DONE |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 3/24/2014 | | 3/24/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/24/2014 | | DONE |
|
|
|
Plan Mod review approved with comments. 3-24-14
|
Miscellaneous action | | | 3/24/2014 | | DONE |
|
|
|
Emailed Mary Froemke & asked if she had concerns with using rate of rise heat detectors instead of fixed at food prep & serving areas. She responded indicating no. Also added that the ceilings are 10' or less.
|
Inspection Record Card- Fire | 3/24/2014 | | 3/24/2014 | | DONE |
Tisha Gallop
|
|
|
|
Permit Ready to Issue | | | 3/24/2014 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 3/24/2014 | | DONE |
Tisha Gallop
|
|
|
called Scott Ramella/Peak Alarm and told him plan mod is ready, fee due.
|
Plan resubmittals received | | | 3/21/2014 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: Recieved two copies of documents and plans; routed to Fire.
|
Override - Parcel Holds | | | 3/14/2014 | | |
|
|
|
|
Issue and Print Permit | | | 3/14/2014 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 3/6/2014 | | 3/11/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 3/11/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 3/11/2014 | | 3/11/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/11/2014 | | DONE |
|
|
|
Plans approved with comments.
|
Telephone call | | | 3/11/2014 | | DONE |
Christina Prado
|
|
|
called Scott to advise permit is ready and gave fees due
|
Override - Parcel Holds | | | 3/11/2014 | | |
|
|
|
|
Permit Ready to Issue | | | 3/11/2014 | | DONE |
Christina Prado
|
|
|
|
Override - Parcel Holds | | | 3/11/2014 | | |
|
|
|
|
Inspection Record Card- Fire | 3/11/2014 | | 3/11/2014 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 3/10/2014 | | |
|
|
|
Received 2 sets
|
Miscellaneous action | | | 3/7/2014 | | DONE |
|
|
|
Received an email from Scott Ramella of Peak Alarm indicating that a new AES dialer was not included in the submittal. I informed Mare Froemke (designer) via email that since the review had not taken place yet that she could resubmit without consequence.
|
Application received | | | 3/6/2014 | | |
|
|
|
|
Case Summary | | | 3/6/2014 | | DONE |
Barbara Stitt
|
|
|
|
Case Summary | | | 3/6/2014 | | DONE |
Barbara Stitt
|
|
|
|