INSP-Final Inspection | 4/8/2014 | 4/8/2014 | 4/8/2014 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 4/4/2014 | 4/7/2014 | 4/7/2014 | P | PEND |
Forrest France
|
|
|
Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 4/1/2014 | 4/2/2014 | 4/2/2014 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic retest passed, verified previous correction items. Final pending project finishes and trade related work.
|
INSP-Final Inspection | 3/31/2014 | 4/1/2014 | 4/1/2014 | P | NR |
Forrest France
|
|
|
C/N items pending, visible leakage and pressure loss at the guage during hydro test, project finishes and remodel work underway.
|
INSP-Sprinkler Rough-in/Hydro | 3/31/2014 | 4/1/2014 | 4/1/2014 | P | FAIL |
Forrest France
|
|
|
Noted corrections include; provide matched temp heads at the first floor mens restroom, provide QR head in the 1st floor storage room, two heads at the glass area exceed min. spacing, combustible concealed space adjacent to the south stairway is not protected, repair leak at the storage closet 1st floor, provide thermal barrier at the dry pendent SW entry.
|
Inspection Record Card- Fire | 3/25/2014 | | 3/25/2014 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 3/25/2014 | | DONE |
Barbara Stitt
|
|
|
|
Issue and Print Permit | | | 3/25/2014 | | DONE |
Barbara Stitt
|
|
|
|
Sprinkler Plan Check | 3/20/2014 | | 3/20/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/20/2014 | | DONE |
Tim Frost
|
|
|
|
Plan assigned to (Tim) | 3/19/2014 | | 3/19/2014 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 3/19/2014 | | 3/19/2014 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 3/19/2014 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 3/19/2014 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Application received | | | 3/14/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 14 2014 3:27PM
|