INSP-Final Inspection | 1/14/2015 | 1/14/2015 | 1/15/2015 | P | PASS |
Forrest France
|
|
|
Noted corrections and adjustments verified. Final inspection passed. Fire alarm permit finaled.
|
INSP-Alarm Testing | 1/12/2015 | 1/13/2015 | 1/13/2015 | A | NR |
Forrest France
|
|
|
Mag locks at exit doors failed to release upon general alarm condition.
|
INSP-Sprinkler Rough-in/Hydro | 1/12/2015 | 1/13/2015 | 1/12/2015 | A | CANC |
Forrest France
|
|
|
As late as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Anderson Inspection cancelled via mobile web on Monday, January 12, 2015.
|
INSP-Final Inspection | 1/9/2015 | 1/9/2015 | 1/12/2015 | P | CANC |
Forrest France
|
|
|
As early as possible Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Monday, January 12, 2015.
|
INSP-Final Inspection | 1/9/2015 | 1/12/2015 | 1/12/2015 | A | FAIL |
Troy Cobbley
|
|
|
For todays inspection I verified audible/visuals for the first and fourth floors including live/work units. I also verified in-duct dectors on the first floor. Only two fire smoke dampers were accessible. All of the others require better access. Elevators and other items were not ready.
|
CHANGE STATUS TO (ISS) | | | 1/9/2015 | | DONE |
|
|
|
|
INSP-Alarm Testing | 1/5/2015 | 1/7/2015 | 1/8/2015 | P | FAIL |
Forrest France
|
|
|
Plan modification will be necessary due to numerous changes to the original design and approved plans including; approx 25 new ID detectors, mag locks at three sets of doors, added smoke and heat detection at the elevator hoistway, relocated sprinkler risers, new ADA rooms and notification appliances, revised matrix, etc. Need to provide notification at the gym restroom, post signage at the FACP room door. Elevator is not in service to complete recall and shunt tests.
|
Miscellaneous action | | | 1/8/2015 | | DONE |
|
|
|
Received an email from Dante Frassa requesting that I open the project for a plan modification submittal.
|
Plan resubmittals received | | | 1/8/2015 | | DONE |
|
|
|
Plan modification drawings received.
|
Alarm Plan Check | 1/8/2015 | | 1/8/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/8/2015 | | DONE |
|
|
|
Plan modification submittal approved with review comments and requirements. Projectdox update.
|
Alarm Plan Check | 4/2/2014 | | 4/2/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/2/2014 | | DONE |
|
|
|
Resubmittal review approved with comments. Projectdox updated.
|
Permit Ready to Issue | | | 4/2/2014 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 4/2/2014 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 4/2/2014 | | 4/2/2014 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 4/1/2014 | | DONE |
|
|
|
|
1st review completed | | | 3/31/2014 | | FAIL |
|
|
|
See 3-31-14 1st review comments.
|
Plan assigned to (Lee) | 3/28/2014 | | 3/28/2014 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 3/28/2014 | | DONE |
|
|
|
I sent an email to Dante requesting clairification. The elevator lobbies on 2, 3 & 4 have hinged doors that look like they are for elevator shaft isolation. I asked if these were fire doors that would need to be tied to the fire alarm system flor closure on alarm.
|
Application received | | | 3/27/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 27 2014 5:06PM
|