Case Summary | | | 2/3/2015 | | |
|
|
|
|
INSP-Final Inspection | 9/11/2014 | 9/12/2014 | 9/12/2014 | A | PASS |
Troy Cobbley
|
|
|
Plan modification approved. Permit finaled
|
CHANGE STATUS TO (ISS) | | | 9/11/2014 | | DONE |
|
|
|
|
(F) Reprint permit | | | 9/11/2014 | | DONE |
|
|
|
|
Alarm Plan Check | 9/9/2014 | | 9/9/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/9/2014 | | DONE |
|
|
|
Resubmittal drawings approved. Taken to front desk for processing.
|
Permit Ready to Issue | | | 9/9/2014 | | |
|
|
|
|
Issue and Print Permit | | | 9/9/2014 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/9/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/9/2014 | | 9/9/2014 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 9/9/2014 | | DONE |
Tisha Gallop
|
|
|
called Mountain alarm and told recep plan mod is ready and fee due.
|
Plan resubmittals received | | | 9/8/2014 | | DONE |
Candy A. Nichols
|
|
|
received 1 set of sheet FA-1, FA-2,FA-3,FA-4- put in fire cubby for Lee M
|
Plan resubmittals received | | | 9/8/2014 | | DONE |
|
|
|
Hard copy plan modification received.
|
INSP-Final Inspection | 8/26/2014 | 8/27/2014 | 8/27/2014 | A | FAIL |
Troy Cobbley
|
|
|
No additional notification devices are needed per Lee but the as-builts need to be approved prior to a final sign off. Any corrections noted on the newly approved plans will need to be implimented.
|
Telephone call | | | 8/27/2014 | | DONE |
|
|
|
Scott Williams called to indicate that Troy Cobbley had approved the system operation, subject to as built review but was looking for backup on defered notification upgrades. I informed him that Scott Arellano and I had discussed this and are allowing the notification upgrades to be be done at a later date for bugetary reasons. I called Troy to let him know this as well.
|
Miscellaneous action | | | 8/27/2014 | | DONE |
|
|
|
Brett Andersen of Mountain alarm submitted as built drawings.
|
Meeting | | | 6/5/2014 | | DONE |
|
|
|
During the weekly meeting I discussed the owners request to change the building notification from 2 to 3 zones, as noted in the previous activity notes, with Scott and Troy. We determined that the request was reasonable. I called Scott Williams back and let him know that they could return to their previouse zone configuration and that the contractor would need to submit a plan modification with details of the changes that would be needed.
|
Telephone call | | | 6/2/2014 | | DONE |
|
|
|
Received a call from Scott Williams - facilities manager, requesting system modifications that will allow 3 seperate zones of notification. He indicated that the system had previously been this way and that they would like to return to that operational function. He indicated that each zone is seperated by a 4 hour wall. 1 zone is admin, 1 is detention and 1 is court rooms. I let him know that I would review this with Scott & Troy and then let him know of our decision.
|
INSP-Final Inspection | 5/8/2014 | 5/13/2014 | 5/13/2014 | A | FAIL |
Troy Cobbley
|
|
|
All alarm audible devices must sync. NFPA 7218.4.2.4, All visual devices must sync NFPA 7218.5.5.4.2, All audible alarm devices shall use "temporal tone" NFPA 7218.4.2.1, All areas/notification shall activate upon alarm IFC907.6, Provide fire alarm notification devices through out all required areas as per IFC 907 and installed per NFPA 72. If wanted provide upgrade agreement, as discussed, to Scott Arellano for review.
|
Telephone call | | | 4/9/2014 | | DONE |
Christina Prado
|
|
|
called Mountain Alarm to advise permit is ready and gave fees due
|
Permit Ready to Issue | | | 4/9/2014 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 4/9/2014 | | 4/9/2014 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 4/9/2014 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 4/7/2014 | | 4/8/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 4/8/2014 | | PASS |
|
|
|
Plans approved regarding fire alarm panel replacement.
|
Alarm Plan Check | 4/8/2014 | | 4/8/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/8/2014 | | DONE |
|
|
|
|
Application received | | | 4/7/2014 | | |
|
|
|
|