INSP-Final Inspection | 8/15/2014 | 8/18/2014 | 8/18/2014 | P | PASS |
Forrest France
|
|
|
C/N items completed. Remainder of fire alarm work passed functional testing and inspection. Permit finaled.
|
INSP-Final Inspection | 8/12/2014 | 8/15/2014 | 8/15/2014 | A | PART |
Forrest France
|
|
|
Items noted include; remove remainder of MP stations per the scope of work, new tamper switch supervision, remove remainder of old horns, clear obstructions at duct detector vent tubes, provide EOL testing for notification circuts on battery power. Duct detectors for unit shutdown tested okay.
|
Telephone call | | | 6/20/2014 | | DONE |
|
|
|
Jason called to let me know they were just informed that an additional sprinkler riser was added that had not been on their original drawings. I told him to note it on the as builts and that a plan mod would not be required unless more changes take place.
|
Permit Ready to Issue | | | 4/15/2014 | | DONE |
Barbara Stitt
|
|
|
|
Issue and Print Permit | | | 4/15/2014 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 4/15/2014 | | 4/15/2014 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Lee) | 4/14/2014 | | 4/14/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 4/14/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 4/14/2014 | | 4/14/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/14/2014 | | DONE |
|
|
|
Plans approved with review comments.
|
Application received | | | 4/9/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 9 2014 2:16PM
|