INSP-Final Inspection | 11/24/2014 | 11/25/2014 | 11/25/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 7/25/2014 | 7/28/2014 | 7/28/2014 | A | PART |
Craig D. Hanson
|
|
|
This was for a the surgery area and waiting room. strobes and chimes pass. partial until rest of area gets completed.
|
INSP-Alarm Testing | 7/25/2014 | 7/25/2014 | 7/25/2014 | P | CANC |
Troy Cobbley
|
|
|
Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Friday, July 25, 2014.
|
Permit Ready to Issue | | | 7/25/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/25/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/25/2014 | | 7/25/2014 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 7/24/2014 | | DONE |
|
|
|
Plan mod includes removal of audible notification but maintains visual notification in the O.R. portion of the project. Area smoke detection inthe O.R. relocated for code compliance with diffuser locations and ceiling configuration.
|
Alarm Plan Check | 7/24/2014 | | 7/24/2014 | | PASS |
Lee G Meredith
|
|
|
Plan Modification approved.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/24/2014 | | DONE |
|
|
|
Plan Mod review approved with additional review comment.
|
Miscellaneous action | | | 7/21/2014 | | DONE |
|
|
|
I received an email from Charlie Bayne requesting a substitution from horn strobes to strobes only in the O.R., as requested in the previous activity from the owner. I informed him that it would be allowed and taht a plan modification would need to be submitted and approved prior to acceptance testing.
|
Miscellaneous action | | | 7/7/2014 | | DONE |
|
|
|
Craig Hanson forwarded me an email from the owner's rep. (Jeff Cramer) requesting a substitution of strobes from horn strobes in the O.R. / C-section area. I responded to Jeff via email indicating this would be allowed but the formal requrest would need to be resubmitted by SimplexGrinnell through a plan modification. Jeff responded to indicated that he directed the general contractor to have SimplexGrinnell to submit the plan mod.
|
Fees Due Hold | 4/16/2014 | | 4/25/2014 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 4/15/2014 | | 4/15/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 4/15/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 4/15/2014 | | 4/15/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/15/2014 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 4/15/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/15/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/15/2014 | | 4/15/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Application received | | | 4/10/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 10 2014 3:48PM
|