Permit Information
Permit NumberFIR14-00210
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1055 N CURTIS RD
Project NameSARMC C-Section OR Remodel
Customer Number 
ePlanReviewYes
Description
C-Section scope is to add FA devices per Engineer Design. Existing FA System in the building to tie to. We are adding a new Transponder panel replacing 2 existing NAC panels, all existing circuits to be reconnected/rewired to the new transponder. Also adding smoke detectors, notification devices, relays for fan control and damper control. The new transponder to be networked to existing FACP located at the entry of the Family Maternity/NICU area. Associated with building permit BLD14-00038.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/24/201411/25/201411/25/2014APASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing7/25/20147/28/20147/28/2014APART
DetailsCraig D. Hanson
This was for a the surgery area and waiting room. strobes and chimes pass. partial until rest of area gets completed.
INSP-Alarm Testing7/25/20147/25/20147/25/2014PCANC
DetailsTroy Cobbley
Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Friday, July 25, 2014.
Permit Ready to Issue  7/25/2014 DONE
Issue and Print Permit  7/25/2014 DONE
Inspection Record Card- Fire7/25/2014 7/25/2014 DONE
DetailsChristina Prado
Plan resubmittals received  7/24/2014 DONE
Plan mod includes removal of audible notification but maintains visual notification in the O.R. portion of the project. Area smoke detection inthe O.R. relocated for code compliance with diffuser locations and ceiling configuration.
Alarm Plan Check7/24/2014 7/24/2014 PASS
DetailsLee G Meredith
Plan Modification approved.
PLANS TAKEN FRONT DESK ALARM  7/24/2014 DONE
Plan Mod review approved with additional review comment.
Miscellaneous action  7/21/2014 DONE
I received an email from Charlie Bayne requesting a substitution from horn strobes to strobes only in the O.R., as requested in the previous activity from the owner. I informed him that it would be allowed and taht a plan modification would need to be submitted and approved prior to acceptance testing.
Miscellaneous action  7/7/2014 DONE
Craig Hanson forwarded me an email from the owner's rep. (Jeff Cramer) requesting a substitution of strobes from horn strobes in the O.R. / C-section area. I responded to Jeff via email indicating this would be allowed but the formal requrest would need to be resubmitted by SimplexGrinnell through a plan modification. Jeff responded to indicated that he directed the general contractor to have SimplexGrinnell to submit the plan mod.
Fees Due Hold4/16/2014 4/25/2014 DONE
Details
Plan assigned to (Lee)4/15/2014 4/15/2014 DONE
DetailsLee G Meredith
1st review completed  4/15/2014 PASS
Alarm Plan Check4/15/2014 4/15/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/15/2014 DONE
Plans approved with review comments.
Permit Ready to Issue  4/15/2014 DONE
Issue and Print Permit  4/15/2014 DONE
Inspection Record Card- Fire4/15/2014 4/15/2014 DONE
DetailsCandy A. Nichols
Application received  4/10/2014 DONE
Application submitted via PDS Online on Apr 10 2014 3:48PM