Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR14-00229
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 521 W BROAD ST
Project NameBogus Brewing Inc.
Customer Number 
ePlanReviewNo
Description
Provide a fire alarm system for sprinkler monitoring. Associated with building permit BLD13-03384.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  2/3/2015  
INSP-Final Inspection5/20/20145/20/20145/20/2014PPASS
DetailsForrest France
Remainder of fire alarm testing completed satisfactory. C/N items finished.
INSP-Final Inspection5/20/20145/20/20145/20/2014APEND
DetailsForrest France
Phone #: ###-#### >> Inspection requested via web by Robert Gobler *Pending fire sprinkler system water supply
INSP-Final Inspection5/18/20145/19/20145/19/2014APART
DetailsForrest France
Final pending water supply for verification of waterflow switch function. Remainder of fire alarm work tested satisfactory including tampers, MP, FACP, RA, trouble conditions, offsite monitoring, etc. Noted a heat detector at the panel has been installed in place of a SD due to adjacent equipment.
Issue and Print Permit  4/24/2014 DONE
Plan assigned to (Lee)4/18/2014 4/22/2014 DONE
DetailsLee G Meredith
1st review completed  4/22/2014 PASS
Alarm Plan Check4/22/2014 4/22/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/22/2014 DONE
Plans approved with review comments.
Telephone call  4/22/2014 DONE
DetailsChristina Prado
called Robert to advise permit is ready and gave fees due
Permit Ready to Issue  4/22/2014 DONE
DetailsChristina Prado
Inspection Record Card- Fire4/22/2014 4/22/2014 DONE
DetailsChristina Prado
Application received  4/18/2014