Case Summary | | | 2/2/2015 | | |
|
|
|
|
INSP-Final Inspection | 8/4/2014 | 8/5/2014 | 8/5/2014 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 7/25/2014 | 7/28/2014 | 7/28/2014 | A | FAIL |
Craig D. Hanson
|
|
|
System is not functioning correctly, not tied into the pre-action valves. Morgan states he needs to do a plan Mod so that more relays can be added.
|
INSP-Alarm Testing | 7/24/2014 | 7/25/2014 | 7/25/2014 | A | FAIL |
Troy Cobbley
|
|
|
The fire sprinkler contractor did not call for a final for his items and is needed to test the tamper and pressure switches on the new dry systems. No inspection performed.
|
Miscellaneous action | | | 6/18/2014 | | DONE |
|
|
|
I received a phone call from Rob Ahten regarding the owners request to change the rack mounted linear heat detection to spot type heat detectors due to fear of damage by fork lifts. Rob followed up with a preliminary design via email prior to a plan mod. Tim Frost and I reviewed it and found it to be acceptable. I emailed Rob to let him know he should proceed with the plan mod.
|
Permit Ready to Issue | | | 5/16/2014 | | DONE |
Barbara Stitt
|
|
|
|
Issue and Print Permit | | | 5/16/2014 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 5/16/2014 | | 5/16/2014 | | DONE |
Barbara Stitt
|
|
|
|
Miscellaneous action | | | 5/12/2014 | | DONE |
|
|
|
I received the valve & panel listings from Rob Ahten. The valve model number was not indicated and the cut sheet for it did not list the approved valve. I requested the model number from Rob. He indicated that Treasure Valley will be supplying the valve and will provide product data for it. Review is on hold until the valve product data is received.
|
Miscellaneous action | | | 5/12/2014 | | DONE |
|
|
|
Rob Ahten submitted the product data for the proper solenoid valve via email.
|
Telephone call | | | 5/12/2014 | | DONE |
|
|
|
I informed tRob Ahten via phone call that key switches for each solenoid are required by NFPA 72 as disconnects and that activating the key switch shall initiate a supervisory signal.
|
Plan assigned to (Lee) | 5/12/2014 | | 5/12/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 5/12/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 5/12/2014 | | 5/12/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/12/2014 | | DONE |
|
|
|
Plan review approved with comments. Projectdox updated.
|
Telephone call | | | 5/9/2014 | | DONE |
|
|
|
Phone call with Rob Ahten - I requested cross listing documents for the releasing solenoids and UL listing of the control panels for releasing. He will email them Monday.
|
Application received | | | 5/8/2014 | | DONE |
|
|
|
Application submitted via PDS Online on May 8 2014 10:09AM
|