Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR14-00274
StatusFinaled
Name PROTEX
Site Address 11193 W EMERALD ST
Project NameFresca Cooler Upgrade
Customer Number 
ePlanReviewYes
Description
Addition of a releasing/detection system tied into the fire alarm system to protect the new cooler systems. There is not associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  2/2/2015  
INSP-Final Inspection8/4/20148/5/20148/5/2014APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection7/25/20147/28/20147/28/2014AFAIL
DetailsCraig D. Hanson
System is not functioning correctly, not tied into the pre-action valves. Morgan states he needs to do a plan Mod so that more relays can be added.
INSP-Alarm Testing7/24/20147/25/20147/25/2014AFAIL
DetailsTroy Cobbley
The fire sprinkler contractor did not call for a final for his items and is needed to test the tamper and pressure switches on the new dry systems. No inspection performed.
Miscellaneous action  6/18/2014 DONE
I received a phone call from Rob Ahten regarding the owners request to change the rack mounted linear heat detection to spot type heat detectors due to fear of damage by fork lifts. Rob followed up with a preliminary design via email prior to a plan mod. Tim Frost and I reviewed it and found it to be acceptable. I emailed Rob to let him know he should proceed with the plan mod.
Permit Ready to Issue  5/16/2014 DONE
DetailsBarbara Stitt
Issue and Print Permit  5/16/2014 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire5/16/2014 5/16/2014 DONE
DetailsBarbara Stitt
Miscellaneous action  5/12/2014 DONE
I received the valve & panel listings from Rob Ahten. The valve model number was not indicated and the cut sheet for it did not list the approved valve. I requested the model number from Rob. He indicated that Treasure Valley will be supplying the valve and will provide product data for it. Review is on hold until the valve product data is received.
Miscellaneous action  5/12/2014 DONE
Rob Ahten submitted the product data for the proper solenoid valve via email.
Telephone call  5/12/2014 DONE
I informed tRob Ahten via phone call that key switches for each solenoid are required by NFPA 72 as disconnects and that activating the key switch shall initiate a supervisory signal.
Plan assigned to (Lee)5/12/2014 5/12/2014 DONE
DetailsLee G Meredith
1st review completed  5/12/2014 PASS
Alarm Plan Check5/12/2014 5/12/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/12/2014 DONE
Plan review approved with comments. Projectdox updated.
Telephone call  5/9/2014 DONE
Phone call with Rob Ahten - I requested cross listing documents for the releasing solenoids and UL listing of the control panels for releasing. He will email them Monday.
Application received  5/8/2014 DONE
Application submitted via PDS Online on May 8 2014 10:09AM