Permit Information
Permit NumberFIR14-00279
StatusFinaled
Name Dante Frassa
Site Address 8800 W EMERALD ST
Project NameTreasure Valley Hospital PH3
Customer Number 
ePlanReviewYes
Description
TVH PH3 scope is to provide total corridor detection for FSD control replacing previous individual in-duct detectors, provide relays for interface with FSD circuits, provide notification on areas not provided on previous submittals, replace existing sprinkler monitor with new monitoring including new pre-action panel equipment, relocate FACP and NACs to its final destination at IT room B166. Associated with building permit BLD13-01688
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/3/201412/4/201412/4/2014APASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing12/3/201412/3/201412/3/2014ADONE
DetailsTroy Cobbley
Finished except for the supervisory signals, low air and tamper, from the pre-action system.
INSP-Alarm Testing8/18/20148/19/20148/19/2014ADONE
DetailsTroy Cobbley
Fire alarm in the Locker Rooms/Storage/PACU areas is complete.
INSP-Alarm Testing8/15/20148/18/20148/18/2014AFAIL
DetailsTroy Cobbley
See the city approved plans for locations where minor corrections and retesting are required.
INSP-Alarm Testing8/13/20148/15/20148/15/2014APART
DetailsCraig D. Hanson
Rough in OK. Phase 2 complete. Could not test alarms no pre-tested inspection documention.
INSP-Alarm Testing8/11/20148/14/20148/13/2014ACANC
DetailsTroy Cobbley
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Wednesday, August 13, 2014.
INSP-Alarm Testing6/23/20146/24/20146/24/2014ADONE
DetailsTroy Cobbley
Lab, Equipment Room and Lobby fire alarm is complete.
Miscellaneous action  6/6/2014 DONE
I received a drawing from Dante Frassa showing the removal of a strobe in the MRI and notation indicating the reasons. I uploadeded it into Tidemark.
Telephone call  6/5/2014 DONE
Dante Frassa called to request the removal of the strobe in the MRI room due to the fact that when the MRI is operating it will cause interference with the fire alarm system. He said that the only time that the room is occupied, there is a medical staff person observing from the control room that is covered with notification. I informed him that this would be acceptable. He will note the change on as built drawings.
Permit Ready to Issue  5/29/2014 DONE
DetailsCandy A. Nichols
Issue and Print Permit  5/29/2014 DONE
DetailsCandy A. Nichols
Inspection Record Card- Fire5/29/2014 5/29/2014 DONE
DetailsCandy A. Nichols
(F) Reprint permit  5/29/2014 DONE
DetailsCandy A. Nichols
Alarm Plan Check5/28/2014 5/28/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/28/2014 DONE
Plans approved with review comments.
Plan resubmittals received  5/27/2014 DONE
Miscellaneous action  5/14/2014 DONE
I received an email from Dante. He indicated that the preaction field equipment is existing and that they are adding a new panel and controls. The room that is covered is C159 - Files. Kitchen hood is existing also.
Telephone call  5/14/2014 DONE
Called Dante and confirmed that the pre-action system for Files Room 159 is water based.
1st review completed  5/14/2014 FAIL
See plan review comments.
Miscellaneous action  5/14/2014 DONE
Emailed review comments to Dante.
Miscellaneous action  5/13/2014 DONE
Email to Dante. Drawing shows preaction equipment with abort switch but doesn't indicate the are being protectied. Need to know what the suppression medium is and if there is pre-alarm notification. Also, there is a kitchen hood that is not indicated on the legend. Need to know if this is existing or new. I let him know that if it is new, it will need a seperate permit.
Plan assigned to (Lee)5/12/2014 5/12/2014 DONE
DetailsLee G Meredith
Application received  5/8/2014 DONE
Application submitted via PDS Online on May 8 2014 4:59PM