Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR14-00281
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 2001 E AMITY RD
Project NameIdaho Power Bldg
Customer Number 
ePlanReviewNo
Description
Replace an existing - non required fire alarm system in a non sprinkled building. Owner has elected to install full coverage detection and notification, including pull stations, smoke and heat detection, duct detector monitoring and monitoring of 2 existing / self contained gas preaction systems. The system will be monitored by Idaho Power throught their SCADA system at a continuously staffed location. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/4/20155/5/20155/5/2015APASS
DetailsKatie Marron
Scope of work complete. Permit finaled.
INSP-Final Inspection4/29/20154/30/20154/30/2015APART
DetailsKatie Marron
Functional test of alarm system complete. Verified previous correction notice items completed satisfactory. Final pending initiating device map posted at FACP and dedicated alarm panel circuit breaker locked out.
Telephone call  10/21/2014 DONE
DetailsCandy A. Nichols
called John to let know his permit is ready and how much is owed
CHANGE STATUS TO (ISS)  10/21/2014 DONE
DetailsTisha Gallop
Alarm Plan Check10/20/2014 10/20/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/20/2014 DONE
Plan Mod submittal approved with no comments. Plans takent to front desk for processing.
Plan resubmittals received  10/15/2014 DONE
DetailsCandy A. Nichols
received alarm plan checklist-2 each sheet FA.00, FA2-0-put in Fire cubby for review
INSP-Final Inspection8/15/20148/22/20148/22/2014ACANC
DetailsTroy Cobbley
Cancel per Demetrie Phone #: ###-####
INSP-Conference8/19/20148/19/20148/19/2014PDONE
DetailsForrest France
Regarding inspection schedule
INSP-Final Inspection7/24/20148/1/20148/1/2014AFAIL
DetailsForrest France
Completed initial walkthrough. Items noted include; lower manual pull stations per note #18 and plan comments, relocate SD at a storage room 1st floor, remove non-functional existing smoke detectors at various locations 1st floor, adjust visual coverage at two rooms in the dispatch center, SD in mens and womens restrooms 1st floor to be located a min. of 3' from HVAC diffusers, missing SD at the storage closet below the stairs 1st floor, add SD at the 2nd floor mens restroom, revise detector coverage at the storage closet 2nd floor, post points map at the panel per review note #24. Knox box per note # 25 is not installed.
Issue and Print Permit  6/2/2014 DONE
Plan assigned to (Lee)5/9/2014 5/14/2014 DONE
DetailsLee G Meredith
1st review completed  5/14/2014 PASS
Alarm Plan Check5/14/2014 5/14/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/14/2014 DONE
Plans approved with review comments.
Inspection Record Card- Fire5/14/2014 5/14/2014 DONE
DetailsBarbara Stitt
Permit Ready to Issue  5/14/2014 DONE
DetailsBarbara Stitt
Telephone call  5/14/2014 DONE
DetailsBarbara Stitt
Left a message for TIm that permit is ready & fees due on 5-14-14 @ 9:35am
Application received  5/9/2014