INSP-Final Inspection | 11/1/2014 | 11/3/2014 | 11/3/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/30/2014 | 10/30/2014 | 10/30/2014 | P | PART |
Troy Cobbley
|
|
|
Tested the protecto wire activation of the deluge system in the new hanger. Functioned as required.
|
INSP-Final Inspection | 9/18/2014 | 9/19/2014 | 9/19/2014 | A | PART |
Troy Cobbley
|
|
|
See the city as-builts for devices marked "ok" that were tested today. As-builts show duplicate addresses in the elevator machine room that will need to be corrected. One smoke detector in the elevator machine room did not recall the elevator.
|
INSP-Final Inspection | 6/5/2014 | 6/6/2014 | 6/6/2014 | A | PART |
Troy Cobbley
|
|
|
A temporary is being given as the work in the riser room and the in-fill is completed except for the elevator recall and related components. All other work outside of the in-fill has not been inspected/tested yet. Resubmittals are required to show the additional flow switch, tamper switch and instead of phone lines a DSC communicator has been installed. No final sign off untill plans are re-approved.
|
INSP-Final Inspection | 6/5/2014 | 6/5/2014 | 6/5/2014 | P | CANC |
Troy Cobbley
|
|
|
Not ready for inspection due to dialer issue
|
Permit Ready to Issue | | | 6/3/2014 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 6/3/2014 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 6/3/2014 | | 6/3/2014 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 6/2/2014 | | DONE |
|
|
|
I received a call from Charlie Bayne confirming that they would be monitoring the existing radionics points during the Infill project.
|
Plan resubmittals received | | | 6/2/2014 | | DONE |
|
|
|
Resubmittals received.
|
1st review completed | | | 6/2/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 6/2/2014 | | 6/2/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/2/2014 | | DONE |
|
|
|
Plans approved with review comments and requirements. Projectdox updated.
|
Plan resubmittals received | | | 5/30/2014 | | DONE |
|
|
|
Resubmittals received
|
Telephone call | | | 5/30/2014 | | DONE |
|
|
|
I spoke with Dante regarding the drawing submittal. I informed him that his current design did not indicated that his new panel would be monitoring existing systems. He informed me that the existing Radionics panel would be monitoring the existing devices. I let him know that this may be possible during the construction period but 2 fire alarm panels would not be allowed for a finished product. He is going to see if they can take over the existing points with their new panel. Drawings were failed on prescreen review.
|
Telephone call | | | 5/30/2014 | | DONE |
|
|
|
Dante call to inform me that they would be monitoring the existing radionics points within the Infill and initial panel replacement project. Drawings were failed on prescreen review. He indicated that he would resubmit revised drawings indicating this on 6/2/14.
|
Plan assigned to (Lee) | 5/27/2014 | | 5/27/2014 | | DONE |
Lee G Meredith
|
|
|
|
Application received | | | 5/21/2014 | | DONE |
|
|
|
Application submitted via PDS Online on May 21 2014 1:52PM
|