Permit Information
Permit NumberFIR14-00316
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 1725 E WARM SPRINGS AVE
Project NameAdams Elementary
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of adding sprinklers to accommodate wall and ceiling configuration. This is an existing building with a new sprinkler system.

This review is for the fire protection below the ceiling ONLY. The attic is not being submitted with this review. Therefore, no occupancy permit may be issued until the attic system is submitted and approved.

*FIELD INSPECTOR*: Please note the above scope of work.

The underground piping was installed under permit FIR14-00277

This project seems to be strictly sprinkler work. Therefore, there does not appear to be an associated building department permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/10/20154/10/20154/10/2015PPASS
DetailsForrest France
Plan modification verified. Scope of work completed, fire sprinkler permit finaled.
INSP-Final Inspection4/10/20154/10/20154/10/2015PPART
DetailsForrest France
Please call Leroy 30 mins prior
Please schedule after 3:30 Phone #: ###-#### Inspection requested via web by Jacci Hunt
Sprinkler Plan Check4/10/2015 4/10/2015 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  4/10/2015 DONE
DetailsTim Frost
CHANGE STATUS TO (ISS)  4/10/2015 DONE
Plan assigned to (Tim)4/1/2015 4/1/2015 DONE
DetailsTim Frost
Sprinkler Plan Check4/1/2015 4/1/2015 FAIL
DetailsTim Frost
INSP-Final Inspection3/27/20153/30/20153/30/2015PPEND
DetailsForrest France
Refer to project activity notes dated 8/15/14
INSP-Final Inspection3/26/20153/27/20153/27/2015ANH
DetailsForrest France
No access
INSP-Sprinkler Rough-in/Hydro8/14/20148/15/20148/15/2014APART
DetailsForrest France
Overhead hydrostatic testing passed. Need to provide plan modification to include field changes in branchline, main and sprinkler head locations and changes to type and number of sprinklers at several locations including the work room, kitchen, office, principal office, east classroom, music office, girls restroom, and storage closets.
INSP-Sprinkler Rough-in7/31/20148/1/20148/1/2014APART
DetailsForrest France
Rough-in inspection completed for the west classroom wing as noted on plans. Missing hangers at classroom 123, lateral brace at the corridor, fire caulk at classroom 126- all corrected while on site. Need to revise spacing issues in classroom #8 room 125. Attic access room and library 130A are incomplete at this time. Remainder of classrooms and corridor are okay for cover per dated annotations.
INSP-Sprinkler Rough-in7/28/20147/30/20147/30/2014ACANC
DetailsTroy Cobbley
Cancel per Roy
Permit Ready to Issue  6/26/2014 DONE
DetailsChristina Prado
Issue and Print Permit  6/26/2014 DONE
DetailsChristina Prado
Inspection Record Card- Fire6/26/2014 6/26/2014 DONE
DetailsChristina Prado
Sprinkler Plan Check6/25/2014 6/25/2014 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  6/25/2014 DONE
DetailsTim Frost
Sprinkler Plan Check6/16/2014 6/16/2014 FAIL
DetailsTim Frost
Miscellaneous action  6/16/2014 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Sprinkler Plan Check6/3/2014 6/3/2014 FAIL
DetailsTim Frost
1st review completed  6/3/2014 FAIL
DetailsTim Frost
Miscellaneous action  6/3/2014 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Plan assigned to (Tim)6/2/2014 6/2/2014 DONE
DetailsTim Frost
Application received  5/29/2014 DONE
Application submitted via PDS Online on May 29 2014 12:09PM