Permit Information
Permit NumberFIR14-00330
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 5301 E WARM SPRINGS AVE
Project NameTerraces of Boise Wings A&B
Customer Number 
ePlanReviewYes
Description
FA submittal on Wings A&B consists on complete notification system, FACP located at the 1st floor Wing C, the FACP will be temporary until the final the entire complex and converted later on to a transponder, tie to the main FACP. Associted with building permit BLD13-00181
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/12/20156/12/20156/12/2015APASS
DetailsThomas Walsh
Final inspection of Wings A & B buildings, including elevator recall functions, and SFDs - PASSED
INSP-Alarm Testing6/8/20156/8/20156/8/2015PPART
DetailsThomas Walsh
Inspection/ test of fire alarm system for the permit coverage area, including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate.
NOTE: No FSDs or elevator functions tested this visit.
INSP-Alarm Testing6/8/20156/15/20156/8/2015PCANC
DetailsThomas Walsh
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, June 08, 2015.
INSP-Sprinkler Rough-in/Hydro6/8/20156/15/20156/8/2015PCANC
DetailsThomas Walsh
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, June 08, 2015.
INSP-Conference1/22/20151/23/20151/23/2015PDONE
DetailsForrest France
On site visit with contractor regarding SA locations at living units- discussed min. distances from HVAC registers, ceiling fans, bathroom doors, cooking appliances, walls, etc. Also noted missing visual notification at ADA unit guest bathrooms and obstructed coverage at units provided with a divided vanity adjacent to the bedroom.
Telephone call  9/24/2014 DONE
Charlie Bayne call to inform me that most of the open area, dwelling unit detectors need to be adjusted from their original position due to the mechanical system return air duct being to close. I told Charlie that as long as the current code requirements were still met, this would be acceptable. Charlie confirmed that they would verify and comply with maximum distances from sleeping rooms and minimum distances from cooking appliances & bathrooms. As built drawings will be required to indicate all relocated locations.
Permit Ready to Issue  6/18/2014 DONE
DetailsBarbara Stitt
Issue and Print Permit  6/18/2014 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire6/18/2014 6/18/2014 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire6/18/2014 6/18/2014 DONE
DetailsBarbara Stitt
Plan resubmittals received  6/17/2014 DONE
Miscellaneous action  6/17/2014 DONE
In review of the drawings resubmittal I found that drawing part 8 has some clutter that is preventing proper review. I emailed Dante to have him make the appropriate corrections.
Alarm Plan Check6/17/2014 6/17/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/17/2014 DONE
Plans approved with review comments. Projectdox updated.
1st review completed  6/4/2014 FAIL
Plan review failed on prescreen. Risers dont match floor plans and calculation sheets. Operational matrix and operational functions are incorrect.
Plan assigned to (Lee)6/3/2014 6/3/2014 DONE
DetailsLee G Meredith
Application received  6/2/2014 DONE
Application submitted via PDS Online on Jun 2 2014 2:03PM