INSP-Final Inspection | 6/12/2015 | 6/12/2015 | 6/12/2015 | A | PASS |
Thomas Walsh
|
|
|
Final inspection of Wings A & B buildings, including elevator recall functions, and SFDs - PASSED
|
INSP-Alarm Testing | 6/8/2015 | 6/8/2015 | 6/8/2015 | P | PART |
Thomas Walsh
|
|
|
Inspection/ test of fire alarm system for the permit coverage area, including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate. NOTE: No FSDs or elevator functions tested this visit.
|
INSP-Alarm Testing | 6/8/2015 | 6/15/2015 | 6/8/2015 | P | CANC |
Thomas Walsh
|
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, June 08, 2015.
|
INSP-Sprinkler Rough-in/Hydro | 6/8/2015 | 6/15/2015 | 6/8/2015 | P | CANC |
Thomas Walsh
|
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, June 08, 2015.
|
INSP-Conference | 1/22/2015 | 1/23/2015 | 1/23/2015 | P | DONE |
Forrest France
|
|
|
On site visit with contractor regarding SA locations at living units- discussed min. distances from HVAC registers, ceiling fans, bathroom doors, cooking appliances, walls, etc. Also noted missing visual notification at ADA unit guest bathrooms and obstructed coverage at units provided with a divided vanity adjacent to the bedroom.
|
Telephone call | | | 9/24/2014 | | DONE |
|
|
|
Charlie Bayne call to inform me that most of the open area, dwelling unit detectors need to be adjusted from their original position due to the mechanical system return air duct being to close. I told Charlie that as long as the current code requirements were still met, this would be acceptable. Charlie confirmed that they would verify and comply with maximum distances from sleeping rooms and minimum distances from cooking appliances & bathrooms. As built drawings will be required to indicate all relocated locations.
|
Permit Ready to Issue | | | 6/18/2014 | | DONE |
Barbara Stitt
|
|
|
|
Issue and Print Permit | | | 6/18/2014 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 6/18/2014 | | 6/18/2014 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 6/18/2014 | | 6/18/2014 | | DONE |
Barbara Stitt
|
|
|
|
Plan resubmittals received | | | 6/17/2014 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/17/2014 | | DONE |
|
|
|
In review of the drawings resubmittal I found that drawing part 8 has some clutter that is preventing proper review. I emailed Dante to have him make the appropriate corrections.
|
Alarm Plan Check | 6/17/2014 | | 6/17/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/17/2014 | | DONE |
|
|
|
Plans approved with review comments. Projectdox updated.
|
1st review completed | | | 6/4/2014 | | FAIL |
|
|
|
Plan review failed on prescreen. Risers dont match floor plans and calculation sheets. Operational matrix and operational functions are incorrect.
|
Plan assigned to (Lee) | 6/3/2014 | | 6/3/2014 | | DONE |
Lee G Meredith
|
|
|
|
Application received | | | 6/2/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 2 2014 2:03PM
|