INSP-Final Inspection | 10/14/2015 | 10/14/2015 | 10/15/2015 | P | PASS |
Thomas Walsh
|
|
|
Final Inspection passed. All previous discrepancies corrected.
|
INSP-Final Inspection | 6/25/2015 | 6/25/2015 | 6/25/2015 | P | PASS |
Thomas Walsh
|
|
|
Final inspection for wings A-D parking garage, including fire pump room. PASSED
|
INSP-Sprinkler Rough-in/Hydro | 6/12/2015 | 6/12/2015 | 6/12/2015 | P | PASS |
Thomas Walsh
|
|
|
Final Inspection of under ground parking for wings A, B C, including the fire pump room. All fire alarm interface, such as waterflow and tampers were tested with the fire alarm system. Riser placards were applied. No discrepancies remained for this portion of the overall system.
|
INSP-Final Inspection | 6/10/2015 | 6/11/2015 | 6/11/2015 | A | PART |
Thomas Walsh
|
|
|
Final inspection of U/G parking garage wet system. NOTE: Fire caulking needed at stair # 3 pipe penetration. Also need to inspect fire pump room, as this room is under this permit.
|
INSP-Sprinkler Rough-in/Hydro | 6/9/2015 | 6/10/2015 | 6/10/2015 | A | PASS |
Thomas Walsh
|
|
|
Boise PDS witnessed fire pump test (Tim Frost and Tom Walsh), incuding pump flow tests to record proper flows and pressures at various stages of the pump operations, also phase reversal, and fire alarm system interface. All tested OK - final fire pump signoff will require room upgrades (1 hour room), including fire rated door installed, emergency lighting, wall penetrations fire stopped, etc. Also all weather sign on exterior of pump room door.
|
Miscellaneous action | | | 6/10/2015 | | DONE |
|
|
|
Performed a miniature fire pump test to verify additional information. The city was not notified of the fire pump test performed by the manufacture representative. The fire pump is rated at 400 Gpm @ 90 Psi, City flow test indicate S-70, R-20, Q-3000
Test as follow
Churn - Inlet had Static of 75 psi outlet was 175 psi
Rate Flow was – 5 pitot from a 2.5” = 333 Gpm, Inlet was 70 Psi and Outlet was 157 Psi
150% was – 11 pitot from a 2.5” = 495 Gpm, Inlet was 67 Psi and Outlet was 134 Psi
The fire pump performed less than anticipated however, the city flow test is more than originally assumed. Therefore, I believe the supply is adequate
|
INSP-Final Inspection | 6/5/2015 | 6/8/2015 | 6/8/2015 | P | PART |
Thomas Walsh
|
|
|
Inspection of fire alarm system interface, including water flows of system risers, tamper devices, control valves, etc. Waterflows came in at approx. 30-40 seconds.All pump room tampers tested OK. All device addresses appeared accurate.
|
Miscellaneous action | | | 5/15/2015 | | PEND |
|
|
|
** FIELD INSPECTOR ** A resubmittal of the pump arrangment is required before this permit can be finaled.
|
INSP-Sprinkler Rough-in/Hydro | 4/21/2015 | 4/21/2015 | 4/23/2015 | P | CANC |
Katie Marron
|
|
|
Cancelled overbooked, rescheduled for later date.
|
Sprinkler Plan Check | 8/4/2014 | | 8/4/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/4/2014 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 8/4/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Issue and Print Permit | | | 8/4/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 8/4/2014 | | 8/4/2014 | | DONE |
Candy A. Nichols
|
|
|
|
(F) Reprint permit | | | 8/4/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Miscellaneous action | | | 7/29/2014 | | DONE |
|
|
|
Sent an email to Trent at Phoenix Fire Protection asking him if he has contacted the GC in regards to the Fire Pump room requirments.
|
Miscellaneous action | | | 7/29/2014 | | DONE |
|
|
|
Contacted the project manger and informed him there is a potential problem in regards to the Fire Pump room. I informed him there are several provisions of NFPA 20 and IFC that must be addressed in regards to the construction of the fire pump room. I sent him my review and a copy of the fire pump room drawing.
|
Sprinkler Plan Check | 7/18/2014 | | 7/18/2014 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 7/18/2014 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Sprinkler Plan Check | 6/20/2014 | | 6/20/2014 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 6/20/2014 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 6/20/2014 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Plan assigned to (Tim) | 6/20/2014 | | 6/20/2014 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 6/11/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 11 2014 10:04AM
|