INSP-Final Inspection | 8/4/2014 | 8/4/2014 | 8/4/2014 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 8/1/2014 | 8/4/2014 | 8/4/2014 | A | FAIL |
Troy Cobbley
|
|
|
Heat detector is mounted too close to a supply register. No testing performed.
|
Telephone call | | | 7/21/2014 | | DONE |
|
|
|
I received a phone call from Rick Groom of Northwest Fire. He indicated that Alarmstar had bid work at this site that they were not capabile of programming due to a proprietary system that Northwest Fire is certified on and the general contractor wants them to provide the programming. I informed him that Alarmstar has the issued permit and that if Alarmstar or the general contractor hires them to provide programming that an additional permit is not required. I also informed him that Alarmstar is still responsible for executing the work by whatever leagal means is available to them.
|
PLANS TAKEN FRONT DESK ALARM | | | 6/27/2014 | | DONE |
|
|
|
Plans approved with comments.
|
Permit Ready to Issue | | | 6/27/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Issue and Print Permit | | | 6/27/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 6/27/2014 | | 6/27/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Plan resubmittals received | | | 6/24/2014 | | DONE |
|
|
|
3rd submittal received.
|
Miscellaneous action | | | 6/24/2014 | | DONE |
|
|
|
Plan submittal approved but waiting for upload confirmation by applicant. I call to let her know this task was required before the permit could be issued. She informed me that there may be a change in the scope. She may resubmit again based on a design revision.
|
Alarm Plan Check | 6/20/2014 | | 6/23/2014 | | FAIL |
Lee G Meredith
|
|
|
Resubmittal candela, load calc incorrect. Heat detector that was submitted was not compatible. I emailed the applicant to let her know that another resubmittal would be required.
|
Telephone call | | | 6/23/2014 | | DONE |
|
|
|
Paula O'Meara called to go over the most recent failure. We discussed the requirements and she will resubmit.
|
Miscellaneous action | | | 6/20/2014 | | DONE |
|
|
|
I emailed the customer to let them know that more information will be required. The heat detector that has been submitted does not appear to be compatible with the existing panel, the battery calcs are incorrect and the candela indicated on the drawing do not match its product data. Resubmittal will be required.
|
Plan resubmittals received | | | 6/17/2014 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/17/2014 | | DONE |
|
|
|
In review of the resubmitted documents, I could not find a referance to the magnetic door holder. I emailed Paula to request additional information.
|
Miscellaneous action | | | 6/17/2014 | | DONE |
|
|
|
I received an email from Paula O'Meara with an incorrect battery calculation form. I responded via email and told her it needed to be corrected and resubmitted prior to review and approval.
|
1st review completed | | | 6/16/2014 | | FAIL |
|
|
|
See 1st review comments.
|
Application received | | | 6/13/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 13 2014 10:33AM
|
Plan assigned to (Lee) | 6/13/2014 | | 6/13/2014 | | DONE |
Lee G Meredith
|
|
|
|