Permit Information
Permit NumberFIR14-00380
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 415 E PARKCENTER BLVD
Project NameSAGE INTERNATIONAL SCHOOL
Customer Number 
ePlanReviewYes
Description
New FA System in an partial existing building. Sage scope is to add notification devices to the entire area of remodel on the school area. We are adding a new FACP panel to take care of the notification and monitoring of existing sprinkler system and duct detectors that being provided by others. Also adding a Zone Card to monitor existing manual stations, smoke and duct detectors and monitor two existing Kitchen Hoods in a pizzeria area. We have to note that the Key Bank area is completely out of scope of work working off their own panel. Associated with building permit BLD14-00884
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/2/2014 DONE
As built drawings received.
INSP-Final Inspection8/10/20148/11/20148/11/2014APASS
DetailsForrest France
Corrections completed. Final inspection passed, fire alarm permit finaled.
INSP-Final Inspection8/8/20148/8/20148/8/2014APART
DetailsForrest France
Verified previous correction items including requested plan mod. Kitchen hood, sprinkler monitoring, and duct detectors tested okay. Final pending voice amplifier repair and points map to be posted at the panel.
Plan resubmittals received  8/7/2014 DONE
Plan resubmittals uploaded by Dante
Alarm Plan Check8/7/2014 8/7/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/7/2014 DONE
Plan modification approved. Original review comments still apply. No new comments. Projectdox updated.
CHANGE STATUS TO (ISS)  8/7/2014 DONE
DetailsChristina Prado
INSP-Alarm Testing8/4/20148/4/20148/4/2014PPART
DetailsForrest France
Completed satisfactory testing of the voice evac and occupant notification appliances. MP stations and SD at the panel tested okay. Items needed prior to final include tie-in and monitoring of the ansul system, test duct detectors and fire sprinkler monitoring, post signage at the door the FACP room. Provide plan modification to reflect changes in field installation from original design including zones, one-lines, location of the panel, number of initiating devices, etc.
Plan assigned to (Lee)6/20/2014 6/20/2014 DONE
DetailsLee G Meredith
1st review completed  6/20/2014 PASS
Alarm Plan Check6/20/2014 6/20/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/20/2014 DONE
Plans approved with drawning notes and review comments.
Permit Ready to Issue  6/20/2014 DONE
DetailsCandy A. Nichols
Issue and Print Permit  6/20/2014 DONE
DetailsCandy A. Nichols
Inspection Record Card- Fire6/20/2014 6/20/2014 DONE
DetailsCandy A. Nichols
(F) Reprint permit  6/20/2014 DONE
DetailsCandy A. Nichols
Miscellaneous action  6/19/2014 DONE
Emailed applicant to request information on the wall seperation between sage school and the pizzaria to determine notification requirements (if any) in the pizzaria.
Application received  6/17/2014 DONE
Application submitted via PDS Online on Jun 17 2014 9:48AM