Miscellaneous action | | | 10/2/2014 | | DONE |
|
|
|
As built drawings received.
|
INSP-Final Inspection | 8/10/2014 | 8/11/2014 | 8/11/2014 | A | PASS |
Forrest France
|
|
|
Corrections completed. Final inspection passed, fire alarm permit finaled.
|
INSP-Final Inspection | 8/8/2014 | 8/8/2014 | 8/8/2014 | A | PART |
Forrest France
|
|
|
Verified previous correction items including requested plan mod. Kitchen hood, sprinkler monitoring, and duct detectors tested okay. Final pending voice amplifier repair and points map to be posted at the panel.
|
Plan resubmittals received | | | 8/7/2014 | | DONE |
|
|
|
Plan resubmittals uploaded by Dante
|
Alarm Plan Check | 8/7/2014 | | 8/7/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 8/7/2014 | | DONE |
|
|
|
Plan modification approved. Original review comments still apply. No new comments. Projectdox updated.
|
CHANGE STATUS TO (ISS) | | | 8/7/2014 | | DONE |
Christina Prado
|
|
|
|
INSP-Alarm Testing | 8/4/2014 | 8/4/2014 | 8/4/2014 | P | PART |
Forrest France
|
|
|
Completed satisfactory testing of the voice evac and occupant notification appliances. MP stations and SD at the panel tested okay. Items needed prior to final include tie-in and monitoring of the ansul system, test duct detectors and fire sprinkler monitoring, post signage at the door the FACP room. Provide plan modification to reflect changes in field installation from original design including zones, one-lines, location of the panel, number of initiating devices, etc.
|
Plan assigned to (Lee) | 6/20/2014 | | 6/20/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/20/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 6/20/2014 | | 6/20/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/20/2014 | | DONE |
|
|
|
Plans approved with drawning notes and review comments.
|
Permit Ready to Issue | | | 6/20/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Issue and Print Permit | | | 6/20/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 6/20/2014 | | 6/20/2014 | | DONE |
Candy A. Nichols
|
|
|
|
(F) Reprint permit | | | 6/20/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Miscellaneous action | | | 6/19/2014 | | DONE |
|
|
|
Emailed applicant to request information on the wall seperation between sage school and the pizzaria to determine notification requirements (if any) in the pizzaria.
|
Application received | | | 6/17/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 17 2014 9:48AM
|