INSP-Final Inspection | 6/26/2014 | 6/27/2014 | 6/27/2014 | A | PASS |
Forrest France
|
|
|
Fire sprinkler work passed inspection. Permit finaled.
|
Permit Ready to Issue | | | 6/26/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Issue and Print Permit | | | 6/26/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 6/26/2014 | | 6/26/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 6/26/2014 | | 6/26/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Plan assigned to (Tim) | 6/26/2014 | | 6/26/2014 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/26/2014 | | 6/26/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 6/26/2014 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/26/2014 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 6/25/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 25 2014 1:21PM
|