Permit Information
Permit NumberFIR14-00438
StatusFinaled
Name PROTEX
Site Address 1500 S EAGLE FLIGHT WAY
Project NameCWI QuailCourt Fire Alarm TI's
Customer Number 
ePlanReviewYes
Description
Fire alarm modification to tenant spaces in the CWI Quail Court facility. Associated with building permit FIR14-00796.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/5/20148/6/20148/6/2014APASS
DetailsForrest France
Verified previous correction items. Functional testing passed. Fire alarm permit finaled.
Alarm Plan Check8/5/2014 8/5/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/5/2014 DONE
Plan modification / as built drawing review approved. Original review comments still apply. No new comments. Projectdox updated. Fee due for added smoke detector and plan modification review = $154.20.
CHANGE STATUS TO (ISS)  8/5/2014 DONE
DetailsTisha Gallop
Plan resubmittals received  8/4/2014 DONE
Plan Mod resubmittals were received under FIR14-00560. I called Jonathan and told him to void that permit and resubmit under the original permit. Inditial review had a few items that were not right compared to what Troy had told me. I called Jonathan & left a message for him to call me to discuss some corrections.
INSP-Alarm Testing7/24/20147/25/20147/25/2014PDONE
DetailsTroy Cobbley
Second floor fire alarm complete. Plan modifications will need to be approved showing the location of the new NAC panel, smoke detector, change in trigger point and the change of notification devices.
INSP-Final Inspection7/21/20147/22/20147/22/2014AFAIL
DetailsTroy Cobbley
Todays testing was for the second floor only. All devices function correctly except a new NAC panel has been installed on the second floor and the new audio devices do not sync with the existing audio devices. Per myself and Lee's conversation with the contractors, plan modifications are required prior to a final sign off for the entire project but the sync issue needs to be addressed prior to second floor occupancy. All fire alarm devices were to function correctly as per phone/email conversation with the fire alarm contractor dated 7/7/2014.
Telephone call  7/7/2014 DONE
Rob Ahten called to let me know he found the site to have 2 existing fire alarm panels. 1 on each floor. The existing Pyrotronics panel triggers the Notifier panel but the Notifier does not trip the Pyro. Also, there are existing devices that do not appear to be required and are randomly placed. I discussed the multiple panels with Scott Arellano. He indicated that if all works properly then it is allowed as an existing condition. If not, corrections need to be made or there can only be one system.
Miscellaneous action  7/7/2014 DONE
I emailed Rob to let him know that since they were existing systems, 2 would be allowed but reset and location signage would be required at each panel, all equipment and functions must work properly and that no required detection in the Area of Work would need removal. Otherwise only 1 system would be allowed. A plan mod will be required either way. Troy Cobbley was copied on the email.
Permit Ready to Issue  6/30/2014 DONE
DetailsChristina Prado
Issue and Print Permit  6/30/2014 DONE
DetailsChristina Prado
Inspection Record Card- Fire6/30/2014 6/30/2014 DONE
DetailsChristina Prado
Application received  6/27/2014 DONE
Application submitted via PDS Online on Jun 27 2014 10:49AM
Plan assigned to (Lee)6/27/2014 6/27/2014 DONE
DetailsLee G Meredith
1st review completed  6/27/2014 PASS
Alarm Plan Check6/27/2014 6/27/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/27/2014 DONE
Plans approved with review comments. Projectdox updated.