Case Summary | | | 2/3/2015 | | |
|
|
|
|
INSP-Final Inspection | 1/22/2015 | 1/27/2015 | 1/27/2015 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Plan resubmittals received | | | 1/20/2015 | | DONE |
|
|
|
Plan modification received.
|
Alarm Plan Check | 1/20/2015 | | 1/20/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/20/2015 | | DONE |
|
|
|
Plan modification approvedwith review comments. Projectdox updated
|
Permit Ready to Issue | | | 1/20/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/20/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/20/2015 | | 1/20/2015 | | DONE |
Brittany Hill
|
|
|
|
INSP-Final Inspection | 12/29/2014 | 12/30/2014 | 12/30/2014 | P | FAIL |
Troy Cobbley
|
|
|
Provide plan modification showing all of the duct smoke detectors including the in-duct detectors and the remoter power supply on the second floor, provide verification the in-duct detectors are with-in their velocity listing for use in the HVAC units, provide verification the smoke detector at the second floor/north stairs is approved to be located outside of code requirements (detector is not shown on plans), install the heat detectors as shown on the approved plans or get approval to delete.
|
INSP-Final Inspection | 10/30/2014 | 10/30/2014 | 10/30/2014 | P | NR |
Forrest France
|
|
|
Items noted include; duct detectors and door holds throughout are not yet ready for testing or inspection, SD's for door holds at two locations second floor need relocated, post signage at the door to the FACP room, zones per plan do not match field install, HD at zone 17 has been deleted- however plans item #6 show to remain, need to provide as-builts reflecting changes prior to final, two knox boxes are posted, MP station is located at the main entry not at the fire riser room. Items tested today include; sprinkler riser supervision, SD at the panel, batteries, Netcon rating, offsite monitoring. Discussed remote indicators for duct detectors.
|
Plan assigned to (Lee) | 7/2/2014 | | 7/2/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/2/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 7/2/2014 | | 7/2/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/2/2014 | | DONE |
|
|
|
Plans approved with review comments. Projectdox updated.
|
Permit Ready to Issue | | | 7/2/2014 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 7/2/2014 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 7/2/2014 | | 7/2/2014 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 6/30/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 30 2014 1:23PM
|