Permit Information
Permit NumberFIR14-00454
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 1875 S CENTURY WAY
Project NameWings Center Pool Addition
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration. Adding a new pool additon

Fire sprinklers used for building area increase. To perform the tenant improvement work within the 3,270 square foot pool addition (shell under permit BLD14-00719 and pool under permit BLD14-00735) and within a 1,014 square foot area within the existing building located next to the pool addition. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, bleachers, changing rooms, a changing room accessible to the disabled, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/3/201412/4/201412/4/2014APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/2/201412/3/201412/3/2014AFAIL
DetailsTroy Cobbley
Missing canopies and shipping clips are still on some of the pendant heads
Telephone call  11/19/2014 DONE
DetailsCandy A. Nichols
called John to let kow that the permit was denied and that he can come pick up
INSP-Sprinkler Rough-in9/16/20149/17/20149/17/2014APASS
DetailsTroy Cobbley
Overhead hydro test passed. Flexible couplings added and branch line restraints provided. Piping can be covered.
INSP-Sprinkler Rough-in9/16/20149/16/20149/16/2014PPART
DetailsTroy Cobbley
Possible need of branchline restraints and need flexible cplgs at the wall penatration and the top and bottom of the 2 1/2" riser. The rest of the rough-in is ok.
INSP-Sprinkler Rough-in/Hydro9/16/20149/17/20149/16/2014ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by John Venche Inspection cancelled from web by: John Venche
INSP-Sprinkler Rough-in9/16/20149/16/20149/16/2014PFAIL
DetailsTroy Cobbley
Could not find the city approved sprinkler plans on site. "Construction plans" were with the approval notes and data sheets.
Plan assigned to (Tim)7/2/2014 7/21/2014 DONE
DetailsTim Frost
Sprinkler Plan Check7/21/2014 7/21/2014 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  7/21/2014 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  7/21/2014 DONE
DetailsTim Frost
Permit Ready to Issue  7/21/2014 DONE
DetailsChristina Prado
Issue and Print Permit  7/21/2014 DONE
Inspection Record Card- Fire7/21/2014 7/21/2014 DONE
DetailsChristina Prado
Telephone call  7/18/2014 PEND
Waiting on sesmic calculations. Everything else is approved.
Application received  7/1/2014 DONE
Application submitted via PDS Online on Jul 1 2014 12:48PM