INSP-Final Inspection | 12/3/2014 | 12/4/2014 | 12/4/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 12/2/2014 | 12/3/2014 | 12/3/2014 | A | FAIL |
Troy Cobbley
|
|
|
Missing canopies and shipping clips are still on some of the pendant heads
|
Telephone call | | | 11/19/2014 | | DONE |
Candy A. Nichols
|
|
|
called John to let kow that the permit was denied and that he can come pick up
|
INSP-Sprinkler Rough-in | 9/16/2014 | 9/17/2014 | 9/17/2014 | A | PASS |
Troy Cobbley
|
|
|
Overhead hydro test passed. Flexible couplings added and branch line restraints provided. Piping can be covered.
|
INSP-Sprinkler Rough-in | 9/16/2014 | 9/16/2014 | 9/16/2014 | P | PART |
Troy Cobbley
|
|
|
Possible need of branchline restraints and need flexible cplgs at the wall penatration and the top and bottom of the 2 1/2" riser. The rest of the rough-in is ok.
|
INSP-Sprinkler Rough-in/Hydro | 9/16/2014 | 9/17/2014 | 9/16/2014 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by John Venche Inspection cancelled from web by: John Venche
|
INSP-Sprinkler Rough-in | 9/16/2014 | 9/16/2014 | 9/16/2014 | P | FAIL |
Troy Cobbley
|
|
|
Could not find the city approved sprinkler plans on site. "Construction plans" were with the approval notes and data sheets.
|
Plan assigned to (Tim) | 7/2/2014 | | 7/21/2014 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/21/2014 | | 7/21/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 7/21/2014 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/21/2014 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 7/21/2014 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 7/21/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/21/2014 | | 7/21/2014 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 7/18/2014 | | PEND |
|
|
|
Waiting on sesmic calculations. Everything else is approved.
|
Application received | | | 7/1/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 1 2014 12:48PM
|