Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR14-00475
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 715 N MITCHELL ST
Project NameHORIZON PARK APTS.
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of 8-unit apartment building. CPVC pipe and extended throw residential sprinklers are being utilized.

Horizon Park - Eight Unit Apartment Building (First floor apt. #s 101,102,103,104, Second floor #s 201,202,203,204). Permit for the construction of a new 2 story, 8 unit apartment building per the approved plans. The building has 4,800 sq. ft. per story including common areas with 4 apartments on each story. This building is fully fire sprinklered per residential occupancy requirements and shall comply with NFPA13 as regulated by the Fire Department. CDM

3/16/2015- Plan Mod #1
Modifications due to field changes.

Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/19/20158/20/20158/20/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro8/18/20158/19/20158/19/2015APASS
DetailsTroy Cobbley
Overhead hydro passed for the second floor
INSP-Sprinkler Rough-in/Hydro8/18/20158/18/20158/18/2015PCANC
DetailsTroy Cobbley
This is a rescheduled overhead hydro. Robert is the contact. Thanks. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro8/17/20158/18/20158/18/2015AFAIL
DetailsTroy Cobbley
Tried to perform overhead hydro test of the 2nd floor twice. It failed both times due to visible loss of pressure at the guage.
Plan assigned to (Tim)8/3/2015 8/3/2015 DONE
DetailsTim Frost
Sprinkler Plan Check8/3/2015 8/3/2015 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  8/3/2015 DONE
DetailsTim Frost
CHANGE STATUS TO (ISS)  8/3/2015 DONE
DetailsChristina Prado
(F) Reprint permit  8/3/2015 DONE
Inspection Record Card- Fire8/3/2015 8/3/2015 DONE
DetailsBrittany Hill
INSP-Sprinkler Rough-in/Hydro3/18/20153/18/20153/18/2015PPART
DetailsTroy Cobbley
Revised plans provided but one piece of pipe installed in the remote area does not match the city approved plans. Also verification needs to be provided for the exposed 2" cpvc pipe can remain exposed. Piping can be covered except for the piping in the remote area until sizing is settled through plan review or changed to match the approved drawings.
Sprinkler Plan Check3/16/2015 3/16/2015 PASS
DetailsTim Frost
Please, see attached comments.
Plan assigned to (Tim)3/16/2015 3/16/2015 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  3/16/2015 DONE
DetailsTim Frost
CHANGE STATUS TO (ISS)  3/16/2015 DONE
DetailsCandy A. Nichols
INSP-Supply line flush2/26/20152/27/20152/27/2015APASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in2/25/20152/25/20152/25/2015PFAIL
DetailsTroy Cobbley
Per review comments plan modifications are needed due to pipe route changes affecting hydraulic calculations. Piping can not be covered and a re-inspection will be required.
INSP-Supply line flush2/25/20152/25/20152/25/2015PCANC
DetailsTroy Cobbley
united water did not turn on water. could not perform flush
INSP-Sprinkler Rough-in9/19/20149/19/20149/19/2014PPASS
DetailsTroy Cobbley
Underground piping is ok to cover
INSP-Sprinkler Rough-in9/8/20149/11/20149/11/2014PCANC
DetailsTroy Cobbley
Cancel per John is the contact. Thanks Phone #: ###-#### Inspection requested via web by Stan Beus
Sprinkler Plan Check7/28/2014 7/28/2014 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  7/28/2014 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  7/28/2014 DONE
DetailsTim Frost
Permit Ready to Issue  7/28/2014 DONE
DetailsBarbara Stitt
Issue and Print Permit  7/28/2014 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire7/28/2014 7/28/2014 DONE
DetailsBarbara Stitt
Plan assigned to (Tim)7/22/2014 7/22/2014 DONE
DetailsScott Arellano
Sprinkler Plan Check7/22/2014 7/22/2014 FAIL
DetailsTim Frost
Prescreen
Application received  7/7/2014 DONE
Application submitted via PDS Online on Jul 7 2014 4:43PM