Miscellaneous action | | | 10/2/2014 | | DONE |
|
|
|
As built drawings received.
|
INSP-Final Inspection | 8/8/2014 | 8/8/2014 | 8/8/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 8/5/2014 | 8/6/2014 | 8/6/2014 | A | PART |
Forrest France
|
|
|
Functional testing completed acceptable. Final pending location of smoke detectors at the north and south corridors 154 and 162 east side of the new fire doors. Relocate away from HVAC diffusers or delete and meet NFPA 72 17.7.5.6.1.
|
INSP-Final Inspection | 8/4/2014 | 8/5/2014 | 8/5/2014 | A | FAIL |
Troy Cobbley
|
|
|
Fire alarm panel is in trouble. Electrician wanted to work on it. No testing performed.
|
Miscellaneous action | | | 8/5/2014 | | DONE |
|
|
|
As built drawings received and uploaded into projectdox. All drawings noted As Built and batch filed into approved drawings folder.
|
INSP-Final Inspection | 8/4/2014 | 8/4/2014 | 8/4/2014 | A | CANC |
Troy Cobbley
|
|
|
Cancel per Brian and I's discussion. Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian A
|
Permit Ready to Issue | | | 7/15/2014 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 7/15/2014 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 7/15/2014 | | 7/15/2014 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 7/11/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 11 2014 9:55AM
|
Plan assigned to (Lee) | 7/11/2014 | | 7/11/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/11/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 7/11/2014 | | 7/11/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/11/2014 | | DONE |
|
|
|
Plans approved with review comments.
|